2021-12-10 11:11:38NFPA 96
  
 10.2.2* A PLACARD SHALL BE CONSPICUOUSLY PLACED NEAR
 EACH EXTINGUISHER THAT STATES THAT THE FIRE PROTECTION
 SYSTEM SHALL BE ACTIVATED PRIOR TO USING THE FIRE
 EXTINGUISHER.
 10.5.1 A READILY ACCESSIBLE MEANS FOR MANUAL ACTIVATION
 SHALL BE LOCATED BETWEEN 1067 MM AND 1219 MM (42 IN.
 AND 48 IN.)ABOVE THE FLOOR, BE ACCESSIBLE IN THE EVENT
 OF A FIRE, BE LOCATEDIN A PATH OF EGRESS, AND CLEARLY
 IDENTIFY THE HAZARD PROTECTED. INDICATE MOUNTING HEIGHT
 AND LOCATION.
 10.5.1.1 AT LEAST ONE MANUAL ACTUATION DEVICE SHALL BE
 LOCATED A MINIMUM OF 3 M (10 FT) AND A MAXIMUM OF 6 M
 (20 FT) FROM THE PROTECTED HOOD EXHAUST SYSTEM(S)
 WITHIN A PATH OF EGRESS
 OR AT AN ALTERNATIVE LOCATION ACCEPTABLE TO THE AHJ.
 INDICATE LOCATION ON A FLOOR PLAN.
  