Plan Review Notes For Permit 21120303 |
Permit Number |
21120303 |
|
Review Stop |
Z |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-03-07 17:10:30 | INSUFFICIENT | | | | 1) THIS LOCATION IS WITHIN A HISTORIC DISTRICT. PLEASE | | PROVIDE A COPY OF THE STATE HISTORIC PRESERVATION | | OFFICE APPROVAL OF THIS LOCATION. | | | | 2) THE SURVEY ONLY PROVIDES THE HEIGHT OF A LIGHT POLE | | AT 12.3 FEET IN HEIGHT IN THE VICINITY OF THE PROPOSED | | WIRELESS FACILITY POLE. PER CITY CODE THIS WILL NOT | | PERMIT THE PROPOSED 32-FOOT-TALL WIRELESS FACILITY | | POLE. THERE APPEARS TO BE A NEARBY POWER POLE THAT IS | | TALLER THAN THE LABELED POLE. PROVIDE THIS HEIGHT | | DIMENSION SO THAT STAFF CAN VERIFY THE PROPOSED | | WIRELESS FACILITY POLE DOES NOT EXCEED THE HEIGHT | | ALLOWANCE. | | | | 3) SHEET C-3 SHOWS THE POLE AT 28 FEET IN HEIGHT. THIS | | CONFLICTS WITH BOTH THE SURVEY AND SITE PLAN HEIGHTS OF | | 32 FEET. ALL PLANS MUST SHOW THE SAME CONDITIONS. | | | | 4) THE HANDHOLE AND BORE PIT NOTES ON SHEET P-1 STATE | | THAT THE SIDEWALK WILL BE RESTORED; HOWEVER, THERE IS | | ALSO PARKWAY AND POSSIBLY CURBING THAT WILL ALSO NEED | | RESTORATION. PLEASE UPDATE THE NOTATIONS ACCORDINGLY. | | | | 5) PROVIDE A CROSS SECTION OF THE UNDERGROUND ELECTRIC | | WHICH VERIFIES THAT THERE ARE NO CONFLICTS WITH | | EXISTING UTILITIES. | | | | 6) THE POLE STYLE MEETS CITY REQUIREMENTS. THE POLE | | COLOR AT THIS LOCATION SHALL BE RAL/RAYCAP 7042 TRAFFIC | | GREY A. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | [email protected] | | |
|