2022-09-21 11:28:59INSUFFICIENT
  
 1) THE LATITUDE AND LONGITUDE COORDINATES FOR THE FINAL
 POLE LOCATION HAVE NOT BEEN UPDATED ON THE SITE PLAN
 AND SURVEY. PLEASE PROVIDE THE CORRECT COORDINATES.
  
 2) THE NEW SURVEY THAT CORRECTLY CALLS OUT THE
 28-FOOT-TALL POLE WAS NOT UPLOADED.
  
 3) THE RELOCATED HANDHOLE BY THE POWER DRAW POLE ON
 SHEET P-1 CORRECTLY ADDRESSES THE LAST SET OF COMMENTS
 (NOTE: SIDEWALK NEEDS TO BE RESTORED TO CITY STANDARDS
 AT THIS LOCATION). THE UPLOAD FOR THIS SHEET LOCATION
 INCLUDED THE ENTIRE JOB PACKAGE. PLEASE ONLY UPLOAD
 SHEET P-1 UNDER THE P-1 TAB. ADDITIONALLY, IT APPEARS
 THAT EVERY SHEET IN THE PACKAGE HAS A NEW "LATEST
 REVISION DATE" AND A NEW ENGINEER OF RECORD SIGNING.
 PLEASE ENSURE THAT THE MOST RECENT VERSION OF EACH
 SHEET IS UPLOADED. THIS DID NOT OCCUR IN ALL INSTANCES.
  
 4) THE POLE STYLE AND HEIGHT MEET CITY REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  