Plan Review Notes
Plan Review Notes For Permit 21120302
Permit Number 21120302
Review Stop Z
Sequence Number 2
Notes
Date Text
2022-08-01 13:31:10INSUFFICIENT
  
 1) REPEAT COMMENT: THE LOCATION OF THE HANDHOLE AND THE
 INSTALL EXCAVATION SHOWN ADJACENT TO THE POLE SUPPLYING
 POWER WILL DAMAGE THE ROOT SYSTEM OF THE EXISTING LARGE
 STREET TREE IF INSTALLED IN THE LOCATION SHOWN ON SHEET
 P-1. THE HANDHOLE MAY NOT BE INSTALLED AT THIS
 LOCATION. *** THE EXCAVATION PIT CONTINUES TO BE SHOWN
 LESS THEN 5 FEET FROM THE TREE, WHICH IS TOO CLOSE. IT
 NEEDS TO BE AT LEAST 10 FEET AWAY, ESPECIALLY GIVEN THE
 SIZE OF THE TREE. STAFF SUGGESTS THAT THE HANDHOLE BE
 INSTALLED UNDER THE SIDEWALK SO THAT IT, AND THE
 EXCAVATION, ARE FURTHER AWAY FROM THE TREE AND IN AN
 AREA THAT TYPICALLY SEES LESS ROOT ZONE EXPANSION.
  
 2) THE POLE STYLE AND HEIGHT MEET CITY REQUIREMENTS.
 THE POLE COLOR AT THIS LOCATION SHALL BE RAL/RAYCAP
 7042 TRAFFIC GREY A.
  