2022-03-30 15:48:15 | INSUFFICIENT |
| |
| 1) THE SURVEY AND ENGINEERING PLANS FAIL TO SHOW TWO |
| PALM TREES THAT ARE LOCATED WITHIN THE BULB OUT WHERE |
| THE POLE IS PROPOSED. PLEASE SHOW THE TREES IN THEIR |
| ACCURATE LOCATIONS SO THAT STAFF CAN VERIFY THAT THERE |
| IS NO CONFLICT WITH THE PROPOSED POLE. |
| |
| 2) THE CITY CODE REQUIRES THAT POLES SHALL BE LOCATED |
| SO AS TO ALIGN WITH EXISTING POLES IN THE RIGHT-OF-WAY |
| AND HAVE EQUAL SETBACK DISTANCES WITH EXISTING POLES |
| FROM THE CURBLINE OF THE RIGHT-OF-WAY. THE PROPOSED |
| POLE IS NOT SHOWN IN LINE WITH THE EXISTING LIGHT POLES |
| ALONG TAMARIND AVENUE IN THIS LOCATION. THE EXISTING |
| LIGHT POLES ARE LOCATED ADJACENT TO THE SIDEWALK (A |
| GOOGLE STREETVIEW SCREENSHOT HAS BEEN PROVIDED TO |
| CHRISTINA WARR). PLEASE ADJUST THE PROPOSED POLE |
| LOCATION ACCORDINGLY. |
| |
| 3) THE ADJACENT LOT IS IN THE APPROVAL PROCESS FOR A |
| RESIDENTIAL BUILDING. IN ORDER TO COMPLY WITH THE CITY |
| CODE REQUIREMENT THAT DOES NOT PERMIT WIRELESS |
| FACILITIES TO BE PLACED IN FRONT OF A RESIDENTIAL |
| STRUCTURE, THE PROPOSED POLE NEEDS TO BE MOVED SOUTH |
| WITHIN THE BULB OUT. STAFF HAS PROVIDED CHRISTINA WARR |
| WITH THE SITE PLAN SHOWING THE SETBACK OF THE RESIDENCE |
| FROM THE BACK OF THE STATE STREET SIDEWALK SO THAT THE |
| POLE LOCATION CAN BE ADJUSTED ACCORDINGLY. |
| 4) THE BORE PIT AND HANDHOLE NOTES ON SHEET P-1 STATE |
| THAT THE SIDEWALK WILL BE RESTORED; HOWEVER, THESE ARE |
| LOCATED ONLY WITHIN THE PARKWAY WHICH WILL NEED |
| RESTORATION. PLEASE UPDATE THE NOTATIONS ACCORDINGLY. |
| |
| 5) THE LOCATION OF THE HANDHOLE AND THE INSTALL |
| EXCAVATION SHOWN ADJACENT TO THE POLE SUPPLYING POWER |
| WILL DAMAGE THE ROOT SYSTEM OF THE EXISTING LARGE |
| STREET TREE IF INSTALLED IN THE LOCATION SHOWN ON SHEET |
| P-1. THE HANDHOLE MAY NOT BE INSTALLED AT THIS |
| LOCATION. |
| |
| 6) THE POLE HEIGHT SHOWN ON SHEET C-3 LISTS THE HEIGHT |
| TO THE TOP OF THE ANTENNA AS 28 FEET ABOVE GRADE; |
| HOWEVER, THE SITE PLAN AND SURVEY CALL OUT A POLE 38 |
| FEET ABOVE GRADE LEVEL. ALL SHEETS MUST SHOW |
| CONSISTENT, ACCURATE INFORMATION. NOTE: THE 38-FOOT |
| HEIGHT IS CONSISTENT WITH ONE OF THE NEARBY POWER |
| POLES. |
| |
| 7) PROVIDE A CROSS SECTION OF THE UNDERGROUND ELECTRIC |
| WHICH VERIFIES THAT THERE ARE NO CONFLICTS WITH |
| EXISTING UTILITIES AND TREE ROOTS. |
| |
| 8) THE PLANS SHOW THE COM LINES WITHIN 2-FEET OF THE |
| BORE PIT(S). IN ORDER TO VERIFY THAT THE INSTALLATION |
| WILL NOT INTERFERE WITH THE EXISTING FACILITIES, |
| PROVIDE A PUBLIC UTILITY LETTER OF NO OBJECTION FROM |
| THE COM PROVIDER(S), MOST LIKELY AT&T OR COMCAST. |
| |
| 9) THE POLE STYLE MEETS CITY REQUIREMENTS. THE POLE |
| COLOR AT THIS LOCATION SHALL BE RAL/RAYCAP 7042 TRAFFIC |
| GREY A. |
| |