2022-01-03 13:29:06 | 1. SITE SURVEY (B-1) REFERENCES OVERHEAD WOODEN | | DISTRIBUTION POLES THAT NO LONGER EXIST WITHIN CURRENT | | STREET VIEW/SITE CONDITIONS, CANNOT REFERENCE OR | | UTILIZE THESE POLES IN ORDER TO ESTABLISH THE HEIGHT OF | | THE ANTENNA POLE. ANTENNA POLE HEIGHT AND COLOR SHALL | | BE ANALOGOUS TO THE EXISTING DECORATIVE CITY STREET | | LAMPS. | | | | 2. CONCRETE CAISSON IS SHOWN ON SURVEY TO CONFLICT WITH | | EXISTING GAS LINE, PLEASE PROVIDE THE NECESSARY PUBLIC | | UTILITY LETTER GRANTING APPROVAL OF THIS PROPOSED POLE | | LOCATION AND DEPTH. | | | | 3. PROPOSED BORE PITS AND HANDHOLE ARE TOO CLOSE TO | | EXISTING PALM TREES, PLEASE ADJUST TO PROVIDE THE | | NECESSARY SPACING TO PROTECT ROOT/TREE VIABILITY. | | RECOMMENDED AT LEAST 8 FT. CLEARANCE FROM PALMS TO | | SAFELY PROVIDE A BUFFER TO THE ROOT SYSTEM. | | | | 4. UNDERGROUND ELECTRICAL VARIES BETWEEN SURVEY (B-1) | | AND PROPOSED POWER ROUTE (P-1), CONFIRM/VALIDATE FINAL | | ELECTRIC ROUTE. | | | | 5. PLEASE PROVIDE A TYPICAL CROSS-SECTION SHOWING THE | | DEPTH OF THE UNDERGROUND ELECTRICAL COMPONENTS. | | | | 6. THE POLE STEALTH DESIGN MEETS CITY STANDARDS. | | | | CHRIS KIMMERLY @ (561)822-1426 | | [email protected] | | |
|