2022-01-03 13:29:061. SITE SURVEY (B-1) REFERENCES OVERHEAD WOODEN
 DISTRIBUTION POLES THAT NO LONGER EXIST WITHIN CURRENT
 STREET VIEW/SITE CONDITIONS, CANNOT REFERENCE OR
 UTILIZE THESE POLES IN ORDER TO ESTABLISH THE HEIGHT OF
 THE ANTENNA POLE. ANTENNA POLE HEIGHT AND COLOR SHALL
 BE ANALOGOUS TO THE EXISTING DECORATIVE CITY STREET
 LAMPS.
  
 2. CONCRETE CAISSON IS SHOWN ON SURVEY TO CONFLICT WITH
 EXISTING GAS LINE, PLEASE PROVIDE THE NECESSARY PUBLIC
 UTILITY LETTER GRANTING APPROVAL OF THIS PROPOSED POLE
 LOCATION AND DEPTH.
  
 3. PROPOSED BORE PITS AND HANDHOLE ARE TOO CLOSE TO
 EXISTING PALM TREES, PLEASE ADJUST TO PROVIDE THE
 NECESSARY SPACING TO PROTECT ROOT/TREE VIABILITY.
 RECOMMENDED AT LEAST 8 FT. CLEARANCE FROM PALMS TO
 SAFELY PROVIDE A BUFFER TO THE ROOT SYSTEM.
  
 4. UNDERGROUND ELECTRICAL VARIES BETWEEN SURVEY (B-1)
 AND PROPOSED POWER ROUTE (P-1), CONFIRM/VALIDATE FINAL
 ELECTRIC ROUTE.
  
 5. PLEASE PROVIDE A TYPICAL CROSS-SECTION SHOWING THE
 DEPTH OF THE UNDERGROUND ELECTRICAL COMPONENTS.
  
 6. THE POLE STEALTH DESIGN MEETS CITY STANDARDS.
  