Plan Review Notes
Plan Review Notes For Permit 21120300
Permit Number 21120300
Review Stop Z
Sequence Number 1
Notes
Date Text
2022-01-04 09:59:141. SITE SURVEY (B-1) IS MISSING AN ADDITIONAL OVERHEAD
 WOODEN DISTRIBUTION POLE, DIRECTLY ADJACENT TO THE POLE
 WHERE THE PROPOSED ELECTRICAL HOOKUP TAKES PLACE.
 PLEASE ADJUST SITE SURVEY AND DRAWINGS TO ACCURATELY
 REFLECT CURRENT SITE CONDITIONS.
  
 2. CONCRETE CAISSON IS SHOWN ON SURVEY TO CONFLICT WITH
 EXISTING GAS LINE, PLEASE PROVIDE THE NECESSARY PUBLIC
 UTILITY LETTER GRANTING APPROVAL OF THIS PROPOSED POLE
 LOCATION AND DEPTH.
  
 3. POLE & UNDERGROUND ELECTRIC SHOWN ON DRAWINGS TO
 CONFLICT WITH EXISTING GAS LINES, PLEASE PROVIDE THE
 NECESSARY PUBLIC UTILITY LETTERS GRANTING APPROVAL OF
 THIS PROPOSED BORE PITS, UNDERGROUND ELECTRIC, AND POLE
 LOCATIONS.
  
 4. PLEASE PROVIDE A TYPICAL CROSS-SECTION SHOWING THE
 DEPTH OF THE UNDERGROUND ELECTRICAL COMPONENTS.
  
 5. THE POLE STEALTH DESIGN MEETS CITY STANDARDS.
  