Plan Review Notes
Plan Review Notes For Permit 21120297
Permit Number 21120297
Review Stop Z
Sequence Number 1
Notes
Date Text
2022-01-31 17:55:31FAILED
  
 1) THE POLE STYLE AND HEIGHT MEET CITY REQUIREMENTS.
  
 2) PLEASE RELOCATE THE POLE IN LINE WITH THE EXISTING
 STREETLIGHT POLE (CLOSER TO THE CURB). THIS WILL PERMIT
 THE INSTALLATION OF A FULL WIDTH SIDEWALK THAT IS NOT
 OBSTRUCTED BY THE POLE AT SUCH TIME THAT THE ADJACENT
 PROPERTY IS DEVELOPED.
 .
 3) THE POLE HEIGHT SHOWN ON SHEET C-3 LISTS THE HEIGHT
 TO THE TOP OF THE ANTENNA AS 28 FEET ABOVE GRADE;
 HOWEVER, THE SITE PLAN AND SURVEY CALL OUT A POLE 32
 FEET ABOVE GRADE LEVEL. ALL SHEETS MUST SHOW
 CONSISTENT, ACCURATE INFORMATION. NOTE: THE 32-FOOT
 HEIGHT IS CONSISTENT WITH ONE OF THE NEARBY POWER
 POLES.
  
 4) THE HANDHOLE AND BORE PIT NOTES ON SHEET P-1 STATE
 THAT THE SIDEWALK WILL BE RESTORED; HOWEVER, THESE ARE
 IN LANDSCAPED AREAS AND NOT OVERLAPPING WITH A
 SIDEWALK. PLEASE UPDATE THE NOTATIONS ACCORDINGLY.
  
 5) THE PLANS SHOW THE BORE PITS BEING DUG WITH AN
 UNDERGROUND ELECTRIC LINE RUNNING THROUGH THEM AND THE
 HANDHOLE INSTALLED ON TOP OF A COMCAST LINE. IN ORDER
 TO VERIFY THAT THE INSTALLATION WILL NOT INTERFERE WITH
 THE EXISTING FACILITIES, PROVIDE A PUBLIC UTILITY
 LETTER OF NO OBJECTION FROM FPL AND COMCAST REGARDING
 THE INSTALLATION.
  
 6) PROVIDE CROSS SECTIONS OF THE UNDERGROUND ELECTRIC
 BORE FOR THE FULL LENGTH OF THE INSTALLATION. THE
 UNDERGROUND ELECTRIC MUST BE CLEARLY SHOWN AVOIDING THE
 UNDERGROUND INFRASTRUCTURE THAT IT CROSSES (EX: WATER,
 SANITARY, ELECTRIC, AND CABLE) AND THE EXISTING PALM
 TREE ROOT STRUCTURE.
  