Plan Review Notes
Plan Review Notes For Permit 21120295
Permit Number 21120295
Review Stop Z
Sequence Number 1
Notes
Date Text
2022-03-09 11:37:30INSUFFICIENT
  
 1) THIS LOCATION IS WITHIN A HISTORIC DISTRICT. PLEASE
 PROVIDE A COPY OF THE STATE HISTORIC PRESERVATION
 OFFICE APPROVAL OF THIS LOCATION.
  
 2) PLEASE CONSIDER MOVING THE POLE SOUTH A FEW FEET SO
 THAT IT IS CENTERED ON THE PROPERTY LINE OF THE PARCELS
 ON THE EAST SIDE OF THE SIDEWALK.
  
 3) THE BORE PIT NOTES ON SHEET P-1 STATE THAT THE
 SIDEWALK WILL BE RESTORED; HOWEVER, THE PARKWAY WILL
 ALSO NEED RESTORATION. PLEASE UPDATE THE NOTATIONS
 ACCORDINGLY.
  
 4) PROVIDE A CROSS SECTION OF THE UNDERGROUND ELECTRIC
 WHICH VERIFIES THAT THERE ARE NO CONFLICTS WITH
 EXISTING UTILITIES.
  
 5) THE PLANS SHOW THE COM LINES WITHIN 2-FEET OF THE
 BORE PIT(S). IN ORDER TO VERIFY THAT THE INSTALLATION
 WILL NOT INTERFERE WITH THE EXISTING FACILITIES,
 PROVIDE A PUBLIC UTILITY LETTER OF NO OBJECTION FROM
 THE COM PROVIDER(S), MOST LIKELY AT&T OR COMCAST.
  
 6) THE POLE STYLE AND HEIGHT MEET CITY REQUIREMENTS.
 THE POLE COLOR AT THIS LOCATION SHALL BE RAL/RAYCAP
 7042 TRAFFIC GREY A.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  