Plan Review Notes
Plan Review Notes For Permit 21120293
Permit Number 21120293
Review Stop Z
Sequence Number 1
Notes
Date Text
2022-01-03 15:00:521. PROVIDED SURVEY IS NOT ACCURATE/COMPLETE. PLEASE
 PROVIDE A COMPLETE SURVEY SHOWING THE FULL SCOPE OF
 WORK.
  
 2. UNDERGROUND ELECTRIC SHOWN ON DRAWINGS TO CONFLICT
 WITH EXISTING SANITATION/SEWER LINE, STORM WATER,
 ELECTRIC, COMMUNICATIONS, AND WATER, PLEASE PROVIDE THE
 NECESSARY PUBLIC UTILITY LETTERS GRANTING APPROVAL OF
 THE PROPOSED BORE PITS, UNDERGROUND ELECTRIC, AND POLE
 LOCATION.
  
 3. PROPOSED BORE PITS AND HANDHOLE ARE TOO CLOSE TO
 EXISTING PALM TREES, PLEASE ADJUST TO PROVIDE THE
 NECESSARY SPACING TO PROTECT ROOT/TREE VIABILITY.
 RECOMMENDED AT LEAST 8 FT. CLEARANCE FROM PALMS TO
 SAFELY PROVIDE A BUFFER TO THE ROOT SYSTEM.
  
 4. ANTENNA POLE COLOR SHALL BE ANALOGOUS TO THE
 EXISTING DECORATIVE CITY STREET LAMPS.
  
 5. THE POLE STEALTH DESIGN MEETS CITY STANDARDS.
  
  