2022-01-03 14:25:101. THE SURVEY DOES NOT ACCURATELY DEPICT THE EXISTING
 CONDITIONS. SPECIFICALLY, THE DISTRIBUTION LINES ARE
 INCORRECTLY DEPICTED. SITE SURVEY (B-1) AND PROPOSED
 POWER ROUTE (P-1) REFERENCES A WOODEN DISTRIBUTION POLE
 THAT NO LONGER EXISTS WITHIN CURRENT STREET VIEW/SITE
 CONDITIONS, ONLY THE CONCRETE POLE REMAINS. THE SURVEY
 AND PLANS NEED TO BE CORRECTED.
  
 2. PLEASE PROVIDE A TYPICAL CROSS-SECTION SHOWING THE
 DEPTH OF THE UNDERGROUND ELECTRICAL COMPONENTS.
  
 3. THE POLE STEALTH DESIGN MEETS CITY STANDARDS.
  
 CHRIS KIMMERLY @ (561)822-1426
 [email protected]
  