Plan Review Notes
Plan Review Notes For Permit 21120284
Permit Number 21120284
Review Stop Z
Sequence Number 1
Notes
Date Text
2022-01-05 11:50:21FAILED
  
 1) THE SITE PLAN NEEDS TO SHOW THE EDGE OF THE EXISTING
 HEDGE AREA AND THE LOCATION OF THE SERVICE GROUND ROD
 SO THAT STAFF CAN VERIFY THAT THERE ARE NO CONFLICTS.
  
 2) THE POLE STYLE AND HEIGHT MEET CITY REQUIREMENTS.
 THE POLE COLOR IS TO BE STEEL/GREY SIMILAR TO AT&T POLE
 AT BELVEDERE AND SOUTH DIXIE.
  
 3) THE HANDHOLE AND BORE PIT NOTES ON SHEET P-1 STATE
 THAT THE SIDEWALK WILL BE RESTORED; HOWEVER, BOTH
 LOCATIONS ARE IN A LANDSCAPED AREA AND DO NOT APPEAR TO
 AFFECT THE SIDEWALK.
  
 4) THE CROSS SECTION OF THE UNDERGROUND ELECTRIC
 INSTALLATION IS REQUIRED TO BE PROVIDED AND INCLUDE THE
 DEPTH OF THE UNDERGROUND INSTALLATION. STAFF MUST
 VERIFY THAT THE ROOT SYSTEM OF THE EXISTING TREE TO THE
 EAST OF THE HANDHOLE IS NOT IMPACTED. VERIFICATION THAT
 THE GAS LINE IS NOT IMPACTED IS ALSO REQUIRED (ALSO SEE
 COMMENT #5).
  
 5) THE PLANS SHOW THE GAS LINE WITHIN 5-FEET OF THE
 EXCAVATION FOR THE HANDHOLE. IN ORDER TO VERIFY THAT
 THE INSTALLATION WILL NOT INTERFERE WITH THE EXISTING
 FACILITIES, PROVIDE A PUBLIC UTILITY LETTER OF NO
 OBJECTION FROM FPU REGARDING THE INSTALLATION.
  