2022-01-05 11:50:21 | FAILED | | | | 1) THE SITE PLAN NEEDS TO SHOW THE EDGE OF THE EXISTING | | HEDGE AREA AND THE LOCATION OF THE SERVICE GROUND ROD | | SO THAT STAFF CAN VERIFY THAT THERE ARE NO CONFLICTS. | | | | 2) THE POLE STYLE AND HEIGHT MEET CITY REQUIREMENTS. | | THE POLE COLOR IS TO BE STEEL/GREY SIMILAR TO AT&T POLE | | AT BELVEDERE AND SOUTH DIXIE. | | | | 3) THE HANDHOLE AND BORE PIT NOTES ON SHEET P-1 STATE | | THAT THE SIDEWALK WILL BE RESTORED; HOWEVER, BOTH | | LOCATIONS ARE IN A LANDSCAPED AREA AND DO NOT APPEAR TO | | AFFECT THE SIDEWALK. | | | | 4) THE CROSS SECTION OF THE UNDERGROUND ELECTRIC | | INSTALLATION IS REQUIRED TO BE PROVIDED AND INCLUDE THE | | DEPTH OF THE UNDERGROUND INSTALLATION. STAFF MUST | | VERIFY THAT THE ROOT SYSTEM OF THE EXISTING TREE TO THE | | EAST OF THE HANDHOLE IS NOT IMPACTED. VERIFICATION THAT | | THE GAS LINE IS NOT IMPACTED IS ALSO REQUIRED (ALSO SEE | | COMMENT #5). | | | | 5) THE PLANS SHOW THE GAS LINE WITHIN 5-FEET OF THE | | EXCAVATION FOR THE HANDHOLE. IN ORDER TO VERIFY THAT | | THE INSTALLATION WILL NOT INTERFERE WITH THE EXISTING | | FACILITIES, PROVIDE A PUBLIC UTILITY LETTER OF NO | | OBJECTION FROM FPU REGARDING THE INSTALLATION. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | [email protected] | | | | | | |
|