2022-03-09 16:34:25 | INSUFFICIENT |
| |
| 1) WHILE A SIDEWALK DOES NOT CURRENTLY EXIST AT THIS |
| PORTION OF 43RD STREET, IF A SIDEWALK IS INSTALLED, IT |
| WILL BE LOCATED AT THE RIGHT-OF-WAY LINE. IN ORDER THAT |
| THE POLE DOES NOT CONFLICT WITH A FUTURE SIDEWALK, THE |
| PLANS MUST CLEARLY SHOW THAT THE ENTIRE POLE, INCLUDING |
| THE MOUNTING BASE, IS LOCATED AT LEAST FIVE FEET FROM |
| THE RIGHT-OF-WAY LINE. THE SETBACK DIMENSIONS THAT HAVE |
| BEEN PROVIDED SEEM TO BE TO THE POLE AND DO NOT INCLUDE |
| THE MOUNTING BASE, WHICH IS SHOWN ON SHEET C-4 AS |
| LARGER THAN THE POLE (NO DIMENSION IS PROVIDED). |
| PROVIDE CLEAR EVIDENCE OF A FIVE-FOOT CLEAR SETBACK |
| FROM THE EDGE OF THE RIGHT-OF-WAY. NOTE THERE IS |
| SUFFICIENT ROOM BETWEEN THE POLE AND THE CURB TO |
| ACCOMMODATE THE SHIFT. |
| |
| 2) THE BORE PIT AND HANDHOLE NOTES ON SHEET P-1 STATE |
| THAT THE SIDEWALK WILL BE RESTORED; HOWEVER, THESE ARE |
| LOCATED ONLY WITHIN THE PARKWAY WHICH WILL NEED |
| RESTORATION. PLEASE UPDATE THE NOTATIONS ACCORDINGLY. |
| |
| 3) PROVIDE A CROSS SECTION OF THE UNDERGROUND ELECTRIC |
| WHICH VERIFIES THAT THERE ARE NO CONFLICTS WITH |
| EXISTING UTILITIES AND TREE ROOTS. |
| |
| 4) THE PLANS SHOW ONE OF THE BORE PITS AND THE POLE |
| INSTALL WITHIN 4 FEET OF A GAS LINE. IN ORDER TO VERIFY |
| THAT THE INSTALLATION WILL NOT INTERFERE WITH THE |
| EXISTING FACILITIES, PROVIDE A PUBLIC UTILITY LETTER OF |
| NO OBJECTION FROM FPU REGARDING THE INSTALLATION. |
| |
| 5) THE POLE STYLE AND HEIGHT MEET CITY REQUIREMENTS. |
| THE POLE COLOR AT THIS LOCATION SHALL BE RAL/RAYCAP |
| 7042 TRAFFIC GREY A. |
| |
| CONTACT ERIC SCHNEIDER @ (561) 822-1446 |
| [email protected] |
| |
| |