Plan Review Notes
Plan Review Notes For Permit 21120282
Permit Number 21120282
Review Stop Z
Sequence Number 1
Notes
Date Text
2022-03-09 16:34:25INSUFFICIENT
  
 1) WHILE A SIDEWALK DOES NOT CURRENTLY EXIST AT THIS
 PORTION OF 43RD STREET, IF A SIDEWALK IS INSTALLED, IT
 WILL BE LOCATED AT THE RIGHT-OF-WAY LINE. IN ORDER THAT
 THE POLE DOES NOT CONFLICT WITH A FUTURE SIDEWALK, THE
 PLANS MUST CLEARLY SHOW THAT THE ENTIRE POLE, INCLUDING
 THE MOUNTING BASE, IS LOCATED AT LEAST FIVE FEET FROM
 THE RIGHT-OF-WAY LINE. THE SETBACK DIMENSIONS THAT HAVE
 BEEN PROVIDED SEEM TO BE TO THE POLE AND DO NOT INCLUDE
 THE MOUNTING BASE, WHICH IS SHOWN ON SHEET C-4 AS
 LARGER THAN THE POLE (NO DIMENSION IS PROVIDED).
 PROVIDE CLEAR EVIDENCE OF A FIVE-FOOT CLEAR SETBACK
 FROM THE EDGE OF THE RIGHT-OF-WAY. NOTE THERE IS
 SUFFICIENT ROOM BETWEEN THE POLE AND THE CURB TO
 ACCOMMODATE THE SHIFT.
  
 2) THE BORE PIT AND HANDHOLE NOTES ON SHEET P-1 STATE
 THAT THE SIDEWALK WILL BE RESTORED; HOWEVER, THESE ARE
 LOCATED ONLY WITHIN THE PARKWAY WHICH WILL NEED
 RESTORATION. PLEASE UPDATE THE NOTATIONS ACCORDINGLY.
  
 3) PROVIDE A CROSS SECTION OF THE UNDERGROUND ELECTRIC
 WHICH VERIFIES THAT THERE ARE NO CONFLICTS WITH
 EXISTING UTILITIES AND TREE ROOTS.
  
 4) THE PLANS SHOW ONE OF THE BORE PITS AND THE POLE
 INSTALL WITHIN 4 FEET OF A GAS LINE. IN ORDER TO VERIFY
 THAT THE INSTALLATION WILL NOT INTERFERE WITH THE
 EXISTING FACILITIES, PROVIDE A PUBLIC UTILITY LETTER OF
 NO OBJECTION FROM FPU REGARDING THE INSTALLATION.
  
 5) THE POLE STYLE AND HEIGHT MEET CITY REQUIREMENTS.
 THE POLE COLOR AT THIS LOCATION SHALL BE RAL/RAYCAP
 7042 TRAFFIC GREY A.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  