Plan Review Notes For Permit 21120281 |
Permit Number |
21120281 |
|
Review Stop |
Z |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-01-28 11:55:58 | FAILED | | | | 1) THE POLE STYLE AND HEIGHT MEET CITY REQUIREMENTS. | | | | 2) THE HANDHOLE AND BORE PIT NOTES ON SHEET P-1 STATE | | THAT THE SIDEWALK WILL BE RESTORED; HOWEVER, THESE ARE | | IN LANDSCAPED AREAS AND NOT OVERLAPPING WITH A | | SIDEWALK. PLEASE UPDATE THE NOTATIONS ACCORDINGLY. | | | | 3) THE PLANS SHOW ONE OF THE BORE PITS BEING DUG | | ADJACENT TO A GAS LINE AND IN CONFLICT WITH AN | | UNDERGROUND ELECTRIC LINE. IN ORDER TO VERIFY THAT THE | | INSTALLATION WILL NOT INTERFERE WITH THE EXISTING | | FACILITIES, PROVIDE A PUBLIC UTILITY LETTER OF NO | | OBJECTION FROM FPU AND FPL REGARDING THE INSTALLATION. | | | | 4) PROVIDE CROSS SECTIONS OF THE UNDERGROUND ELECTRIC | | FOR THE FULL LENGTH OF THE INSTALLATION. THE | | UNDERGROUND ELECTRIC MUST BE CLEARLY SHOWN AVOIDING THE | | UNDERGROUND INFRASTRUCTURE AND ANY TREE ROOT SYSTEMS | | THAT IT CROSSES (EX: WATER LINE). | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | [email protected] | | | | |
|