Plan Review Notes
Plan Review Notes For Permit 21120281
Permit Number 21120281
Review Stop Z
Sequence Number 1
Notes
Date Text
2022-01-28 11:55:58FAILED
  
 1) THE POLE STYLE AND HEIGHT MEET CITY REQUIREMENTS.
  
 2) THE HANDHOLE AND BORE PIT NOTES ON SHEET P-1 STATE
 THAT THE SIDEWALK WILL BE RESTORED; HOWEVER, THESE ARE
 IN LANDSCAPED AREAS AND NOT OVERLAPPING WITH A
 SIDEWALK. PLEASE UPDATE THE NOTATIONS ACCORDINGLY.
  
 3) THE PLANS SHOW ONE OF THE BORE PITS BEING DUG
 ADJACENT TO A GAS LINE AND IN CONFLICT WITH AN
 UNDERGROUND ELECTRIC LINE. IN ORDER TO VERIFY THAT THE
 INSTALLATION WILL NOT INTERFERE WITH THE EXISTING
 FACILITIES, PROVIDE A PUBLIC UTILITY LETTER OF NO
 OBJECTION FROM FPU AND FPL REGARDING THE INSTALLATION.
  
 4) PROVIDE CROSS SECTIONS OF THE UNDERGROUND ELECTRIC
 FOR THE FULL LENGTH OF THE INSTALLATION. THE
 UNDERGROUND ELECTRIC MUST BE CLEARLY SHOWN AVOIDING THE
 UNDERGROUND INFRASTRUCTURE AND ANY TREE ROOT SYSTEMS
 THAT IT CROSSES (EX: WATER LINE).
  