Plan Review Notes For Permit 21120280 |
Permit Number |
21120280 |
|
Review Stop |
Z |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-01-05 14:24:56 | PROPOSED POLE LOCATION IS SUBJECT TO SPECIAL EVENTS | | REVIEW. ALL COMMENTS BELOW ARE PENDING THE LOCATION | | APPROVAL FROM SPECIAL EVENTS. | | | | 1. PROPOSED POWER ROUTE, BORE PIT, AND UNDERGROUND | | ELECTRICAL CONNECTION IS SHOWN TO POTENTIALLY CONFLICT | | WITH EXISTING GAS LINE, SEWER, AND WATER, PLEASE | | PROVIDE THE NECESSARY UTILITY LETTERS GRANTING APPROVAL | | OF THIS ELECTRICAL CONNECTION LOCATION AND DEPTH. | | | | 2. PROPOSED BORE PITS AND HANDHOLE ARE TOO CLOSE TO | | EXISTING PALM TREES, PLEASE ADJUST TO PROVIDE THE | | NECESSARY SPACING TO PROTECT ROOT/TREE VIABILITY. | | RECOMMENDED AT LEAST 8 FT. CLEARANCE FROM PALMS TO | | SAFELY PROVIDE A BUFFER TO THE ROOT SYSTEM. | | | | 3. PLEASE PROVIDE A TYPICAL CROSS-SECTION SHOWING THE | | DEPTH OF THE UNDERGROUND ELECTRICAL COMPONENTS. | | | | 4. PROPOSED LOCATION IS SUBJECT TO SPECIAL EVENTS | | APPROVAL. | | | | 5. THE POLE STEALTH DESIGN MEETS CITY STANDARDS. | | | | CHRIS KIMMERLY @ (561)822-1426 | | [email protected] | | |
|