Plan Review Notes For Permit 21120274 |
Permit Number |
21120274 |
|
Review Stop |
Z |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-01-28 10:26:26 | FAILED | | | | 1) THE POLE STYLE AND HEIGHT MEET CITY REQUIREMENTS. | | | | 2) PLEASE RELOCATE THE POLE ADJACENT TO THE PROPERTY | | LINE INSTEAD OF IN THE MIDDLE OF THE SWALE AREA | | (GENERALLY IN LINE WITH THE FIRE HYDRANT). THIS WILL | | PERMIT THE INSTALLATION OF A FULL WIDTH SIDEWALK THAT | | IS NOT OBSTRUCTED BY THE POLE AT SUCH TIME THAT THE | | ADJACENT PROPERTY IS DEVELOPED. | | | | 3) THE HANDHOLE AND BORE PIT NOTES ON SHEET P-1 STATE | | THAT THE SIDEWALK WILL BE RESTORED; HOWEVER, THE BORE | | PITS ARE IN SWALE AREAS WITHOUT SIDEWALKS AND THE | | HANDHOLE IS PROPOSED WHERE THERE IS SOME ASPHALT BUT | | NOTHING THAT CAN ACCURATELY BE DESCRIBED AS A SIDEWALK. | | PLEASE UPDATE THE NOTATIONS ACCORDINGLY. | | | | 4) THE PLANS SHOW ONE OF THE BORE PITS BEING DUG | | ADJACENT TO A GAS LINE. IN ORDER TO VERIFY THAT THE | | INSTALLATION WILL NOT INTERFERE WITH THE EXISTING | | FACILITIES, PROVIDE A PUBLIC UTILITY LETTER OF NO | | OBJECTION FROM FPU REGARDING THE INSTALLATION. | | | | 5) PROVIDE CROSS SECTIONS OF THE UNDERGROUND ELECTRIC | | FOR THE FULL LENGTH OF THE INSTALLATION. THE | | UNDERGROUND ELECTRIC MUST BE CLEARLY SHOWN AVOIDING THE | | UNDERGROUND INFRASTRUCTURE THAT IT CROSSES (EX: WATER, | | SANITARY AND GAS LINES). | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | [email protected] | | |
|