2022-01-31 17:00:42 | FAILED |
| |
| 1) THE POLE STYLE AND HEIGHT MEET CITY REQUIREMENTS. |
| |
| 2) THE CITY CODE REQUIRES THAT WIRELESS FACILITIES IN |
| THE RIGHT-OF-WAY MAY WITHIN RESIDENTIAL DISTRICTS MAY |
| NOT BE PLACED DIRECTLY IN FRONT OF A RESIDENTIAL |
| STRUCTURE. PLEASE SHIFT THE POLE TO THE NORTH SO THAT |
| IT IS IN LINE WITH OR SLIGHTLY PAST THE FRONT FACADE OF |
| THE HOUSES ON EITHER SIDE OF EITHER SIDE OF MANNING |
| AVENUE. |
| |
| 3) THE POLE HEIGHT SHOWN ON SHEET C-3 LISTS THE HEIGHT |
| TO THE TOP OF THE ANTENNA AS 28 FEET ABOVE GRADE; |
| HOWEVER, THE SITE PLAN AND SURVEY CALL OUT A POLE 32 |
| FEET ABOVE GRADE LEVEL. ALL SHEETS MUST SHOW |
| CONSISTENT, ACCURATE INFORMATION. NOTE: THE 32-FOOT |
| HEIGHT IS CONSISTENT WITH ONE OF THE NEARBY POWER |
| POLES. |
| |
| 4) THE HANDHOLE AND BORE PIT NOTES ON SHEET P-1 STATE |
| THAT THE SIDEWALK WILL BE RESTORED; HOWEVER, THESE ARE |
| IN LANDSCAPED AREAS AND NOT OVERLAPPING WITH A |
| SIDEWALK. PLEASE UPDATE THE NOTATIONS ACCORDINGLY. |
| |
| 5) THE PLANS SHOW THE BORE PITS BEING DUG ADJACENT TO |
| AN UNDERGROUND ELECTRIC LINE. IN ORDER TO VERIFY THAT |
| THE INSTALLATION WILL NOT INTERFERE WITH THE EXISTING |
| FACILITIES, PROVIDE A PUBLIC UTILITY LETTER OF NO |
| OBJECTION FROM FPL REGARDING THE INSTALLATION. |
| |
| 6) THE EDGE OF THE BORE PIT EXCAVATION ON THE EAST SIDE |
| OF MANNING AVENUE, WEST OF THE HANDHOLE BY THE POWER |
| POLE MUST BE RELOCATED AT LEAST FIVE FEET FROM THE |
| TRUNK OF THE EXISTING PALM TREE. THE CURRENT LOCATION |
| WILL DAMAGE THE ROOT SYSTEM OF THE EXISTING PALM TREE |
| AND IS NOT PERMITTED. |
| |
| 7) THE UNDERGROUND ELECTRIC BORE ON THE BORING PROFILE |
| MUST BE CLEARLY SHOWN AVOIDING THE UNDERGROUND |
| INFRASTRUCTURE IN THE RIGHT-OF-WAY (EX: WATER AND |
| SANITARY LINES). PROVIDED THE SEPARATION IS MET IN |
| COMMENT #6, THE 36-INCH DEPTH WILL AVOID THE PALM TREE |
| ROOT SYSTEMS THAT IT CROSSES. |
| |