2021-12-09 10:29:55 | 12/09/21 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. WOULD YOU PLEASE HAVE A SIGNATURE ON THE ISOMETRIC |
| DRAWING OF THE PERSON DESIGNING THE SYSTEM, NOT IN |
| ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE |
| 61G15-23.001, FLORIDA STATUTE 471 PER THE WPB |
| AMENDMENTS TO THE FBC SEC. 107.1 GENERAL. |
| |
| 2. THE CITY OF WEST PALM BEACH HAS A RECORD OF A GAS |
| PERMIT FOR A GENERATOR AND A TANK-LESS. THE BTU LOAD OF |
| THE EXISTING GAS SYSTEM MUST BE ADDED TO THE TOTAL BTU |
| LOAD TO ENSURE THE EXISTING SYSTEM IS PROPERLY SIZED. |
| IF UNDERSIZED, THE EXISTING SYSTEM MUST BE REDONE TO |
| ENSURE A SAFE OPERATING SYSTEM. SUBMIT A GAS PIPING |
| RISER DIAGRAM THAT SHOWS THE TYPE OF EXISTING |
| APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE PIPE |
| SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE |
| DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT |
| OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF |
| THE SECTION PER THE 2020 FBC RES. SECS. G2412.4, |
| G2412.8, G2413.1, G2413.2, G2413.3. |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| |
| WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON |
| REQUEST |
| |