2022-03-15 11:22:58 | INSUFFICIENT |
| |
| 1) UPDATED COMMENT: THE RESPONSE STATES THAT FPL WILL |
| BE UTILIZING THEIR EASEMENT TO INSTALL THE UNDERGROUND |
| ELECTRIC FROM THE POWER POLE ON PRIVATE PROPERTY TO THE |
| NEW HANDHOLE IN THE 44TH STREET RIGHT-OF-WAY. YOU MUST |
| PROVIDE VERIFICATION OF THE EASEMENT. THE BEST METHOD |
| IS ON A SURVEY; HOWEVER, RECORDED DOCUMENTATION THAT |
| CLEARLY IDENTIFIES THIS LOCATION IS ALSO ACCEPTABLE. |
| FPL STATING THEY HAVE AN EASEMENT, DOES NOT VERIFY THAT |
| THEY HAVE AN EASEMENT. PLEASE NOTE, IF NO EASEMENT |
| EXISTS, NOTARIZED AUTHORIZATION FROM THE PRIVATE |
| PROPERTY OWNER FOR THE USE OF THEIR PROPERTY FOR THE |
| VERIZON UNDERGROUND ELECTRIC IS ALSO ACCEPTABLE. IF NO |
| EASEMENT IS PRESENT AND YOU ARE UNABLE TO SECURE |
| AUTHORIZATION FROM THE PRIVATE PROPERTY OWNER, THE |
| UNDERGROUND ELECTRIC MUST COME FROM AN ALTERNATIVE |
| LOCATION. |
| |
| 2) UPDATED COMMENT: THANK YOU FOR PROVIDING A PARTIAL |
| CROSS OF THE UNDERGROUND ELECTRIC ALONG 44TH STREET; |
| HOWEVER, AS THIS IS A CITY RIGHT-OF-WAY, THE CROSS |
| SECTION NEEDS TO INCLUDE THE ENTIRE BORE LENGTH, NOT A |
| GAP FOR THE AREA BETWEEN 90 FEET AND 120 FEET. |
| |
| 3) BASED ON THE LOCATION OF THE PROPERTY LINE IN |
| RELATIONSHIP TO THE SIDEWALKS SHOWN ON THE SURVEY, THE |
| SITE PLAN AND POWER ROUTE PLAN THAT ARE OVERLAID ON THE |
| AERIAL DO NOT ALIGN. PLEASE REVIEW AND CORRECT. |
| |
| 4) THE POLE STYLE AND HEIGHT MEET CITY REQUIREMENTS. |
| THE POLE COLOR AT THIS LOCATION SHALL BE RAL/RAYCAP |
| 7042 TRAFFIC GREY A. |
| |
| CONTACT ERIC SCHNEIDER @ (561) 822-1446 |
| [email protected] |
| |