Plan Review Notes For Permit 21120225 |
Permit Number |
21120225 |
|
Review Stop |
ENG |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-06-23 15:57:13 | 1) WHILE STAFF DOES NOT SUPPORT THE PROPOSED LOCATION, | | THE FOLLOWING COMMENTS WILL NEED TO BE TAKEN INTO | | ACCOUNT NO MATTER WHERE THE NEW POLE AND UNDERGROUND | | ELECTRIC ARE PLACED | | A. PLEASE PROVIDE PROFILE FOR PROPOSED UNDERGROUND | | ELECTRIC SHOWING ALL CROSSING DATA FOR OTHER UTILITIES. | | B. ALL ROADWAY, SIDEWALK, AND SWALE RESTORATIONS ARE | | REQUIRED PER CITY STANDARD. | | C. CITY UTILITIES ARE SHOWN INCORRECTLY ON PLANS. | | PLEASE CONTACT JANICE TARBILL, [email protected] FOR | | AS-BUILT INFORMATION. PLEASE INCLUDE AS-BUILT | | INFORMATION IN YOUR RESUBMITTAL. | | | | SUZANNE BERGLUND | | [email protected] | | 561-951-1180 | | |
|