Plan Review Notes For Permit 21120211 |
Permit Number |
21120211 |
|
Review Stop |
Z |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-01-03 16:29:02 | FAILED | | | | 1) THE SURVEY AND ENGINEERING SITE PLANS NEED TO SHOW | | THE ENTIRE UNDERGROUND ELECTRIC PATH. THE SURVEY NEEDS | | TO SHOW THE RIGHT-OF-WAY LINE FOR THE ENTIRE LENGTH OF | | THE INSTALLATION SO THAT STAFF CAN VERIFY THAT THE | | UNDERGROUND ELECTRIC IS FULLY WITHIN THE RIGHT-OF-WAY. | | | | 2) PROVIDE CROSS SECTIONS OF THE LOCATION OF THE | | UNDERGROUND ELECTRIC FOR THE FULL LENGTH OF THE | | INSTALLATION ALONG 55TH STREET. THERE UNDERGROUND | | ELECTRIC MUST BE CLEARLY SHOWN AVOIDING THE STREET TREE | | ROOT SYSTEMS AND ANY INFRASTRUCTURE THAT IT CROSSES | | (EXAMPLE THE SANITARY LINE SHOWN ON THE SURVEY). | | | | THE COMMUNICATIONS FACILITY IS SHOWN MEETING CITY | | REQUIREMENTS. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | [email protected] | | |
|