2022-04-15 18:27:00 | ROOFING REVIEW: |
| |
| ORIGINAL COMMENT: |
| 1- FLAT ROOF NOA 15-1020.02 SUBMITTED: |
| CLEARLY MARK/IDENTIFY WHICH ASSEMBLY IS GOING TO BE |
| INSTALLED. IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN |
| PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED |
| RAS 117 CALCULATIONS ARE REQUIRED. SEE GENERAL |
| LIMITATION #7 ON LAST PAGE OF NOA SUBMITTED. |
| NOTE: FASTENING OPTIONS WITH GENERAL LIMITATION #9 CAN |
| NOT BE USED IF THEY DON'T MEET THE DESIGN PRESSURES OF |
| ALL ROOF ZONES. SEE GENERAL LIMITATION #9 ON LAST PAGE |
| OF NOA. |
| |
| RESPONSE: |
| REPEAT COMMENT. NOT ADDRESSED. |
| NOTE: LOOKING AT THE NOA FOR THE SECOND TIME, I |
| REALIZED THIS NOA IS FOR RECOVER DECK APPLICATIONS NOT |
| FOR NEW CONSTRUCTION. I APOLOGIZE. NEED TO PROVIDE |
| PRODUCT APPROVAL FOR WOOD DECKS AND THE SAME COMMENTS |
| APPLY. NEED TO SPECIFY THE ASSEMBLY TO BE INSTALLED. |
| THIS CAN BE SUBMITTED FOR REVIEW LATER AS A DEFERRED |
| SUBMITTAL. ADVICE IF SUBMITTING LATER. |
| |
| 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| NOTE: CLARIFY WHY SUBMITTING PRODUCT APPROVAL FOR |
| SINGLE HUNG WINDOWS. PLANS DON'T SHOW ANY. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |