Plan Review Notes For Permit 21120145 |
Permit Number |
21120145 |
|
Review Stop |
R |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-02-28 13:30:01 | ROOFING REVIEW: | | | | 1- FLAT ROOF NOA 15-1020.02 SUBMITTED: | | CLEARLY MARK/IDENTIFY WHICH ASSEMBLY IS GOING TO BE | | INSTALLED. IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN | | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED | | RAS 117 CALCULATIONS ARE REQUIRED. SEE GENERAL | | LIMITATION #7 ON LAST PAGE OF NOA SUBMITTED. | | NOTE: FASTENING OPTIONS WITH GENERAL LIMITATION #9 CAN | | NOT BE USED IF THEY DON'T MEET THE DESIGN PRESSURES OF | | ALL ROOF ZONES. SEE GENERAL LIMITATION #9 ON LAST PAGE | | OF NOA. | | | | 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | NOTE: CLARIFY WHY SUBMITTING PRODUCT APPROVAL FOR | | SINGLE HUNG WINDOWS. PLANS DON'T SHOW ANY. | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | QUESTIONS REGARDING THESE COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|