2021-12-29 11:04:08 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 21120145 |
| 12/29/2021 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) NO PLUMBING PLANS HAVE BEEN SUBMITTED FOR THE NEW |
| ACCESSORY STRUCTURE. CLARIFY IF ANY PLUMBING FIXTURES |
| ARE TO BE INSTALLED AND PROVIDE PLUMBING PLANS AND |
| ISOMETRIC DRAWINGS IF APPLICABLE- SEC. 107.2.1 & |
| 107.3.5.3 WPB. |
| |
| 2) PLEASE NOTE THAT TWO DWELLINGS ON THE SAME, OR |
| CONSTRUCTION OF A COMMERCIAL BUILDING ON THE PROPERTY |
| WILL REQUIRE INSTALLATION OF A POTABLE WATER SERVICE |
| BACKFLOW PREVENTER DEVICE IN ACCORDANCE WITH THE WPB |
| DEPT. OF UTILITIES CROSS-CONNECTION CONTROL MANUAL. |
| PLEASE NOTE A SEPARATE PERMIT WILL BE REQUIRED TO |
| INSTALL A REDUCED PRESSURE ZONE (RPZ) BACKFLOW AT THE |
| WATER METER- CHAPTER C (PAGE 12 WPB CROSS-CONNECTION |
| MANUAL. |
| |
| A FL. LICENSED PLUMBING CONTRACTOR SHALL OBTAIN A |
| SEPARATE PERMIT FOR INSTALLATION OF THE BACKFLOW |
| PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB AND SEC. |
| 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL BE |
| TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT |
| PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. |
| PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS |
| DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. |
| |
| PLEASE NOTE ADDITIONAL COMMENTS MAY OCCUR UPON REVIEW |
| OF RESUBMITTED PLANS. WHEN RESUBMITTING, IT IS HELPFUL |
| TO PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG |
| WITH THE CITY RE-SUBMITTAL FORM. |
| |