2022-02-28 13:28:58RESIDENTIAL (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21120145
  
 1- ENERGY CALCULATIONS SUBMITTED:
 A)ENERGY CALCULATIONS FORM R405-2020 IS REQUIRED TO BE
 CERTIFIED AT THE BOTTOM BY THE OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY
 THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 B)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 C)PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM, INCLUDING OWNER'S NAME, BUILDER'S NAME. NOTE:
 ADDRESS ASSIGNED TO THIS STRUCTURE IS 819 NATHAN HALE
 RD. REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 C)REVISE WINDOWS OVERHANG DEPTH AND SEPARATION TO MATCH
 PLANS. SEC. R101.5.1.1.2 FBC-. ENERGY CONSERVATION.
 NOTE: SEE EXTERIOR ELEVATIONS.
  
 2- LOT DRAINAGE
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING: R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY
 AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
 NOTE: DRAINAGE PLAN TO SHOW THE EXISTING AND PROPOSED
 GRADE ELEVATIONS SHOWING HOW KEEPING WATER AWAY FROM
 ADJACENT PROPERTIES.
  
 3- ENGINEER OF RECORD NEEDS TO SPECIFY COMPLETE DESIGN
 CRITERIA:
 A)SPECIFY THE CURRENT CODE IN EFFECT, FBC-RESIDENTIAL
 7TH EDITION (2020).
 B)BUILDING EXPOSURE, MEAN ROOF HEIGHT, ETC.
 C)ULTIMATE AND NOMINAL WIND SPEEDS.
 D)COMPONENTS AND CLADDING DESIGN PRESSURES FOR ROOF AND
 WALLS.
 E)ALL ROOF AND FLOOR LIVE AND DEAD LOADS.
 SEC. R301.2.1 FBC RESIDENTIAL.
  
 4- ENGINEER OF RECORD TO PROVIDE COMPLETE WALL SECTION
 AND SPECIFICATIONS. SPECIFY ALL FRAMING MEMBERS AND ALL
 CONNECTORS AT EACH END. SPECIFY EXTERIOR AND INTERIOR
 FINISHES, WALL SHEATHING THICKNESS AND FASTENING, ETC.
 SEC. R301.1 FBC-RESIDENTIAL AND SEC. 107.3.5.3 CITY
 AMENDMENTS.
  
 5- ENGINEER OF RECORD TO PROVIDE COMPLETE ROOF FRAMING
 PLAN AND SPECIFICATIONS. SPECIFY ALL FRAMING MEMBERS
 AND ALL CONNECTORS AT EACH END. SPECIFY EXTERIOR AND
 INTERIOR FINISHES, ETC. SEC. R301.1 FBC-RESIDENTIAL AND
 SEC. 107.3.5.3 CITY AMENDMENTS.
  
 6- DESIGNER OF RECORD TO NEEDS TO DEPICT THE BUILDING
 THERMAL ENVELOPE (WALLS AND CEILING) AND SPECIFY
 INSULATION MATERIALS AND THEIR R-VALUES. SEC. R103.2
 FBC-ENERGY CONSERVATION.
 NOTE: KEEP IN MIND THICKENS OF CEILING AND WALLS WHEN
 SPECIFYING INSULATION R-VALUES. IF SPECIFYING FOAM
 INSULATION, THEN PROVIDE FOAM INSULATION ICC EVALUATION
 REPORT. THIS REPORT NEEDS TO BE REVIEWED/APPROVED IN
 WRITING BY THE DESIGNER OF RECORD.
  
 7- SHEET S1:
 A)COLUMN SCHEDULE DOESN'T PROVIDE SPECIFICATIONS FOR
 STEEL COLUMN BASE PLATE. PROVIDE COMPLETE INFORMATION.
 SEC. R301.1 FBC-RESIDENTIAL. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 B) WHERE IS DETAIL S1-5, 1/SD1, 4/SD1 AND 6/SD1
 SPECIFIED ON PLANS. ALSO, CLEARLY IDENTIFY EACH PLAN.
 ONLY THE FOUNDATION PLAN WAS IDENTIFIED. SEC. R301.1
 FBC-RESIDENTIAL. SEC. 107.2.1 CITY AMENDMENTS.
  
 C)CLEARLY IDENTIFY EACH FLOOR PLAN. ONLY THE FOUNDATION
 PLAN WAS IDENTIFIED. ALSO, FLOR PLAN DOESN'T MATCH
 FLOOR FLOOR PLAN. MISSING ALL THE PARTITIONS. AND,
 CLEARLY IDENTIFY EACH ROOM. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 D)SPECIFY ROOF SLOPE AS REQUIRED BY SEC. R905.11.1
  
 E)SPECIFY ROOF SHEATHING THICKNESS, NAIL TYPE, SIZE AND
 SPACING AS REQUIRED BY SEC. R803.2 FBC-RESIDENTIAL AND
 AND TABLE R803.2.3.1 FBC-RESIDENTIAL.
 NOTE: RING SHANK NAILS ARE REQUIRED.
  
 F) PROVIDE DOOR AND WINDOW STRUCTURAL BUCK DETAIL
 SHOWING COMPLIANCE WITH SEC. R609.7.2.1
 FBC-RESIDENTIAL. SPECIFY STRUCTURAL BUCK SIZE AND
 FASTENING.
 NOTE: STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO
 THE DOOR/WINDOW FRAME AS REQUIRED BY SEC. R609.7.2.1
 FBC-RESIDENTIAL.
  
 G)ENGINEER TO PROVIDE COMPLETE WELDING SPECIFICATIONS
 AT ALL STRUCTURAL CONNECTIONS OF BEAMS, STEEL ANGLES,
 ETC. SEC. R301.1 FBC-RESIDENTIAL. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 H)LOW SLOPE ROOFS: PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR ROOF DRAINS AND OVERFLOW DRAINS AS
 REQUIRED BY SEC. R903.4.1 FBC-RESIDENTIAL.
 PROVIDE DETAILS: SPECIFY SIZE AND LOCATION ON ROOF.
  
 8- MISSING DRAWING SD1. DRAWING UPLOADED TO PROJECTDOX
 IS FOR A/C INFORMATION. PROVIDE CORRECT SD1 DRAWING.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 9- FLAT ROOF NOA 15-1020.02 SUBMITTED:
 CLEARLY MARK/IDENTIFY WHICH ASSEMBLY IS GOING TO BE
 INSTALLED. IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED. SEE GENERAL
 LIMITATION #7 ON LAST PAGE OF NOA SUBMITTED.
 NOTE: FASTENING OPTIONS WITH GENERAL LIMITATION #9 CAN
 NOT BE USED IF THEY DON'T MEET THE DESIGN PRESSURES OF
 ALL ROOF ZONES. SEE GENERAL LIMITATION #9 ON LAST PAGE
 OF NOA.
  
 10- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 NOTE: CLARIFY WHY SUBMITTING PRODUCT APPROVAL FOR
 SINGLE HUNG WINDOWS. PLANS DON'T SHOW ANY.
  
 11- ALL DRAWINGS SUBMITTED NEED THE NAME AND SIGNATURE
 OF THE DESIGNER OF RECORD AS REQUIRED BY SEC. 107.2.1
 CITY AMENDMENTS.
  
 12-VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. UPDATE VALUATION TO INCLUDE ALL COSTS,
 INCLUDING DESIGN PROFESSIONAL FEES FOR BUILDING
 OFFICIAL APPROVAL.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved