Plan Review Notes
Plan Review Notes For Permit 21120094
Permit Number 21120094
Review Stop E
Sequence Number 2
Notes
Date Text
2021-12-21 14:25:14FAILED SECOND ELECTRIC REVIEW
  
 1) PROVIDE CLARITY IN DOCUMENTS SUBMITTED. INCLUDE
 EQUIPMENT, CONDUCTORS WIRING METHODS, NOTING WHAT IS
 NEW AND WHAT IS EXISTING FROM POINT OF ORIGIN TO
 UTILIZATION EQUIPMENT. DETAIL EXISTING LOADS AND LOAD
 CALCULATIONS FOR ALL EQUIPMENT WHETHER EXISTING OR NEW.
 THE WORK SCOPE FOR THE PROJECT STATES" INSTALL SERVICE
 WIRES FROM METER CAN TO NEW 200 AMP PANEL AND INSTALL
 GFI RECEPTACLE FOR TEMPORARY POWER" IF THIS IS
 INACCURATE THEN PLEASE SUBMIT A CORRECT WORK SCOPE. FBC
 107.2
  
 2) VALUE IS STATED AT $650. PLEASE PROVIDE AN ACCURATE
 VALUATION FOR PROJECTS SUBMITTED AS PER THE W.P.B.
 AMENDMENT 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved