2022-01-03 20:06:361ST REVIEW FBC-2020 PLUMBING
 PERMIT-21120068
 1/3/2022
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020
 FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH
 EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1. I HAVE RESEARCHED CITY RECORDS BACK TO 0000 AND
 THERE IS NO RECORD OF A PERMIT FOR THE INSTALLATION OF
 ANY GAS AT THIS ADDRESS.SINCE THERE IS NO RECORD OF A
 PERMIT FOR THE GAS, THE EXISTING GAS LINES SHALL
 CONSIDERED AS NEW. WPB AMENDMENTS TO THE FBC SEC.
 105.1.
  
 2. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2020 FBC FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2020 FBC FUEL GAS RES
 SECS. G2413.4.1, G2413.4.2.
  
 3. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. TYPE OF GAS (LP OR NATURAL). WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 5. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. 2020 FBC FUEL GAS SEC.
 409.4, FBC FUEL GAS RES. SEC. G2420.4.
  
 6. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2020 FBC FUEL GAS
 SECS. 401.8 THROUGH 402.6.1 AND TABLES 402.4 (1)
 THROUGH 402.4 (37) OR 2020 FBC FUEL GAS RES. SEC.
 G2413.
  
 7. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2020 FBC
 FUEL GAS SEC. 402.4.1 OR 2017 FBC FUEL GAS RES. SEC.
 G2413.4.1.
  
 8. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2020 FBC FUEL GAS SEC. 402.2 OR 2020
 FBC FUEL GAS RES. SEC. G2413.2.
  
 9. SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2020 FBC FUEL GAS SEC.305.1 OR
 2020 FBC FUEL GAS RES. SEC. G2408.1.
  
 10. SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE
 DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR
 ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM 2020 FBC FUEL GAS SEC. 402.3 OR 2020 FBC FUEL
 GAS RES. SEC. G2413.3
  
 11. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2020 FBC FUEL GAS SEC.410.1 OR 2020 FBC
 FUEL GAS RES. SEC. G2421.1.
  
 12. GAS RISER DIAGRAM REQUIRED WPB AMENDMENTS TO THE
 FBC SEC. 107.3.5.3 (12) RESIDENTIAL GAS
  
 13. INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER
 IS THE ONLY GAS APPLIANCE IN THIS SYSTEM? IF NOT,
 SUBMIT A COMPLETE GAS RISER SHOWING ALL PIPE SIZES,
 TYPE OF PIPE, THE DEVELOPED LENGTH TO THE FURTHEST GAS
 OUTLET, THE BTU LOAD OF EACH APPLIANCE, THE PSI OF THE
 SYSTEM, THE TYPE OF GAS AND THE TOTAL BTU LOAD ON THE
 SYSTEM. THESE REQUIREMENTS ALSO APPLY TO A NEW GAS
 SYSTEM. WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12)
 RESIDENTIAL GAS
  
 14. SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMENDMENTS TO THE FBC SEC. 107.2.1.
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 15. INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER
 IS REPLACING AN EXISTING TANKLESS WATER HEATER OR IS IT
 REPLACING A STORAGE TANK TYPE WATER HEATER OR IS IT
 BEING ADDED TO THE EXISTING HOT WATER SYSTEM? INDICATE
 ON THE APPLICATION IN THE DESCRIPTION OF WORK. WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS
  
 16. SUBMIT TWO COPIES OF THE TABLE FOR INSTALLATION
 CLEARANCES FROM THE RINNAI INSTALLATION MANUAL. THE
 MANUAL REQUIRES A CLEARANCE OF EITHER 4 FEET OR 12
 INCHES FROM ANY OPERABLE WINDOWS OR DOORS. SHOW THE
 LOCATION OF ALL OPERABLE WINDOWS AND DOORS ON THE PLAN
 AND THE DISTANCE OF THE TANKLESS WATER HEATER FROM
 EACH. WPB AMENDMENTS TO THE FBC SEC. 107.2.1.
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  