Date |
Text |
2022-01-03 20:06:36 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT-21120068 |
| 1/3/2022 |
| |
| CODES IN EFFECT: |
| |
| FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH |
| EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION |
| 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH |
| EDITION 2020 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1. I HAVE RESEARCHED CITY RECORDS BACK TO 0000 AND |
| THERE IS NO RECORD OF A PERMIT FOR THE INSTALLATION OF |
| ANY GAS AT THIS ADDRESS.SINCE THERE IS NO RECORD OF A |
| PERMIT FOR THE GAS, THE EXISTING GAS LINES SHALL |
| CONSIDERED AS NEW. WPB AMENDMENTS TO THE FBC SEC. |
| 105.1. |
| |
| 2. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| LENGTH OF ALL CUT SECTIONS OF PIPE PER 2020 FBC FUEL |
| GAS, SECS. 402.4.1, 402.4.2. OR 2020 FBC FUEL GAS RES |
| SECS. G2413.4.1, G2413.4.2. |
| |
| 3. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR |
| EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 4. TYPE OF GAS (LP OR NATURAL). WPB AMENDMENTS TO THE |
| FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 5. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| AHEAD OF EACH MP REGULATOR. 2020 FBC FUEL GAS SEC. |
| 409.4, FBC FUEL GAS RES. SEC. G2420.4. |
| |
| 6. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| BTU LOAD ON THE SYSTEM. REFER TO THE 2020 FBC FUEL GAS |
| SECS. 401.8 THROUGH 402.6.1 AND TABLES 402.4 (1) |
| THROUGH 402.4 (37) OR 2020 FBC FUEL GAS RES. SEC. |
| G2413. |
| |
| 7. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2020 FBC |
| FUEL GAS SEC. 402.4.1 OR 2017 FBC FUEL GAS RES. SEC. |
| G2413.4.1. |
| |
| 8. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| ON THE PLAN PER 2020 FBC FUEL GAS SEC. 402.2 OR 2020 |
| FBC FUEL GAS RES. SEC. G2413.2. |
| |
| 9. SUBMIT MANUFACTURER?S SPECIFICATION |
| SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| VERIFY COMPLIANCE WITH 2020 FBC FUEL GAS SEC.305.1 OR |
| 2020 FBC FUEL GAS RES. SEC. G2408.1. |
| |
| 10. SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE |
| DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS |
| OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR |
| ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS |
| SYSTEM 2020 FBC FUEL GAS SEC. 402.3 OR 2020 FBC FUEL |
| GAS RES. SEC. G2413.3 |
| |
| 11. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| INSTALLATION. 2020 FBC FUEL GAS SEC.410.1 OR 2020 FBC |
| FUEL GAS RES. SEC. G2421.1. |
| |
| 12. GAS RISER DIAGRAM REQUIRED WPB AMENDMENTS TO THE |
| FBC SEC. 107.3.5.3 (12) RESIDENTIAL GAS |
| |
| 13. INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER |
| IS THE ONLY GAS APPLIANCE IN THIS SYSTEM? IF NOT, |
| SUBMIT A COMPLETE GAS RISER SHOWING ALL PIPE SIZES, |
| TYPE OF PIPE, THE DEVELOPED LENGTH TO THE FURTHEST GAS |
| OUTLET, THE BTU LOAD OF EACH APPLIANCE, THE PSI OF THE |
| SYSTEM, THE TYPE OF GAS AND THE TOTAL BTU LOAD ON THE |
| SYSTEM. THESE REQUIREMENTS ALSO APPLY TO A NEW GAS |
| SYSTEM. WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) |
| RESIDENTIAL GAS |
| |
| 14. SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE |
| LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION |
| AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER |
| HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND |
| DRAWN. WPB AMENDMENTS TO THE FBC SEC. 107.2.1. |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 15. INDICATE ON THE PLAN IF THE TANKLESS WATER HEATER |
| IS REPLACING AN EXISTING TANKLESS WATER HEATER OR IS IT |
| REPLACING A STORAGE TANK TYPE WATER HEATER OR IS IT |
| BEING ADDED TO THE EXISTING HOT WATER SYSTEM? INDICATE |
| ON THE APPLICATION IN THE DESCRIPTION OF WORK. WPB |
| AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON |
| CONSTRUCTION DOCUMENTS |
| |
| 16. SUBMIT TWO COPIES OF THE TABLE FOR INSTALLATION |
| CLEARANCES FROM THE RINNAI INSTALLATION MANUAL. THE |
| MANUAL REQUIRES A CLEARANCE OF EITHER 4 FEET OR 12 |
| INCHES FROM ANY OPERABLE WINDOWS OR DOORS. SHOW THE |
| LOCATION OF ALL OPERABLE WINDOWS AND DOORS ON THE PLAN |
| AND THE DISTANCE OF THE TANKLESS WATER HEATER FROM |
| EACH. WPB AMENDMENTS TO THE FBC SEC. 107.2.1. |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| ATELYO BELISLE |
| PLUMBING INSPECTOR / |
| PLUMBING PLAN REVIEW |
| AVAILABLE FROM 1:00 PM TO 4:00 PM |
| [email protected] |
| 561-805-6695 |
| |
| |