Plan Review Notes
Plan Review Notes For Permit 21120055
Permit Number 21120055
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2022-03-31 12:57:15PLAN SET ADDRESSES COMMENT ON PRIOR REVIEW REGARDING
 FIRE SPRINKLER AND UNDERGROUND FIRE MAIN. ANY WORK ON
 SPRINKLER AND UNDERGROUND MUST HAVE SHOP DRAWINGS/PLANS
 SUBMITTED UNDER SERPARATE PERMITS AND WORK MUST BE
 COMPLETED BY CERTIFIED INSTALLER.
  
 PROVISO: PLAN REFERRS TO INSTALLATION OF FIRE ALARM,
 PLEASE SUBMIT SHOP DRAWINGS COMPLIANT WITH NFPA 72 TO
 BE REVIEWED AND APPROVED UNDER A SEPARATE PERMIT.
  
 PER CITY ORDINANCE, ALL WORK IS SUBJECT TO FIELD
 TESTING AND INSPECTION FOR APPROVAL.
  