2022-01-07 17:38:42 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 21120055 |
| 1/7/2022 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) LS-1 OR P-5: PROVIDE PLUMBING FIXTURE CALCULATIONS |
| FOR EACH WAREHOUSE TENANT SPACE IN COMPLIANCE WITH |
| TABLE 403.1 FBC P. PROVIDE A SCHEDULE ON THE PLAN THAT |
| INDICATES THE REQUIRED AND PROVIDED NUMBER OF FIXTURES |
| FOR THE MIXED OCCUPANCIES OF B AND S-1. PLEASE NOTE FOR |
| MIXED OCCUPANCIES FRACTIONAL NUMBERS FOR EACH OCCUPANCY |
| SHALL FIRST BE SUMMED AND THEN ROUNDED UP TO THE NEXT |
| WHOLE NUMBER- SEC. 403.1.1 FBC P. |
| |
| 2) PLEASE PROVIDE A LIST OF REQUIRED SEPARATE PERMITS |
| ON THE PLANS INCLUDING THE POTABLE WATER SERVICE |
| BACKFLOW PREVENTER, IRRIGATION SYSTEM, FIRE LINE, FIRE |
| SPRINKLER, FIRE LINE BACKFLOW PREVENTER, IRRIGATION |
| SYSTEM BACKFLOW PREVENTER- SECS. 105.1 & 107.2.1 WPB. |
| |
| 3) PROVIDE ENLARGED TOILET ROOM AND BREAKROOM DRAWINGS |
| AND THE FOLLOWING LIST OF MISSING ACCESSIBILITY DETAILS |
| IN ACCORDANCE WITH FBC ACC: |
| A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| WATER CLOSETS- SEC. 604.3. |
| B) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| LAVATORIES- 606.2. |
| C) TURNING SPACE DIAGRAMS AND DIMENSIONS- 304.3. |
| D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE |
| WALLS- 604.2. |
| E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| FLOORS- 604.4. |
| F) HEIGHTS OF THE LAVATORY SINK RIMS OR COUNTER |
| SURFACES FROM THE FINISHED FLOOR- 606.3. |
| G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO |
| THE REFLECTIVE SURFACES- 603.3 |
| H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4, |
| FIGURES 604.5.1 & 604.5.2. |
| I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS- 604.6. |
| J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED |
| FROM THE FRONTS OF THE WATER CLOSETS- SEC. AND FIGURE |
| 604.7. |
| K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- 606.2 |
| L) DRINKING FOUNTAINS: REFER TO SECTIONS 306, 307, AND |
| 602 FBC ACC AND PROVIDE DRINKING FOUNTAIN INSTALLATION |
| DETAILS AND ELEVATION VIEWS SHOWING KNEE AND TOE |
| CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS. SHOW |
| THE REQUIRED 30 X 48 IN. CLEAR FLOOR SPACE FOR A |
| FORWARD WHEELCHAIR APPROACH TO THE FOUNTAIN- SEC. 602.2 |
| AND SHOW HOW THE LOCATIONS OF THE FOUNTAINS WILL BE IN |
| COMPLIANCE WITH SEC. 307.2 PROTRUSION LIMITS. |
| M) CLEAR FLOOR SPACE APPROACH DIAGRAMS AND DIMENSIONS |
| AT THE BREAKROOM SINK, DISHWASHER AND REFRIGERATOR- |
| SECS. 305, 606.2, 804.6.3 & 804.6.6. |
| N) HEIGHT OF THE BREAKROOM SINK RIM OR COUNTER SURFACE |
| FROM THE FINISHED FLOOR- 606.3. |
| O) PROVIDE AN ELEVATION DETAIL OR NOTE TO VERIFY THE |
| FREEZER INSIDE THE REFRIGERATOR HAS A MINIMUM OF 50 |
| PERCENT OF FREEZER SPACE 54-INCHES MAXIMUM FROM THE |
| FINISHED FLOOR- 804.6.6. |
| |
| 4) P1 & P4: PROVIDE A FLOOR CLEANOUT FOR THE 4-INCH |
| DRAIN LINE IN AN ACCESSIBLE LOCATION FOR WAREHOUSE 104- |
| SECS. 708.1.1 & 708.1.10 FBC P. |
| |
| 5) P-2 & P4: PROVIDE A SHUTOFF VALVE AT THE ENTRANCE OF |
| THE 1-INCH WATER DISTRIBUTION PIPE INTO WAREHOUSE 107- |
| SEC. 606.1 (2) FBC P. |
| |
| 6) P5: THE HWR LINE SHALL BE ROUTED TO THE COLD WATER |
| INLET PIPE OF THE WATER HEATER AND THE COLD WATER INLET |
| PIPE OR THE HOT WATER RETURN CONNECTION OF THE |
| THERMOSTATIC MIXING VALVE- SEC. 607.2.2 FBC P. |
| |
| 7) P5: PROVIDE AN EQUIPMENT SCHEDULE FOR THE WATER |
| HEATER INDICATING MAKE, MODEL, GALLON SIZE AND |
| EFFICIENCY RATING- SEC. 502.1 FBC P & C404.2 FBC EC. |
| |
| 8) REVISE THE ENERGYGAUGE COMPLIANCE FORM TO INCLUDE |
| THE WATER HEATER AND PIPE INSULATION DATA- C101.5, |
| C403, & C404 FBC EC. |
| |
| 9) P-3: PROVIDE THE MAIN ROOF GUTTER SIZES AND GPM FLOW |
| AT EACH DOWNSPOUT LOCATION- SECS. 1106.3 & 1106.6 FBC |
| P. |
| |
| 10) A-3.1 & P-3: PLEASE PROVIDE CANOPY ROOF DRAINAGE |
| CALCULATIONS AND GUTTER AND DOWNSPOUT SIZES- SEC. |
| 1106.1 FBC P. A) SHOW THE DOWNSPOUT LOCATIONS ON THE |
| PLAN. B) PROVIDE GUTTER AND DOWNSPOUT CONNECTION AND |
| BUILDING ATTACHMENT DETAILS- SEC. 1106.1 FBC P. |
| |
| 11) P-3: PROVIDE A DETAIL SHOWING THE TRANSITION |
| FITTING BETWEEN THE DOWNSPOUT AND THE STORM DRAIN PIPE- |
| SEC. 1106.1 FBC P. |
| |
| 12) P-3 & C2.1: SHOW THE UNDERGROUND STORM DRAIN PIPE |
| SIZES- SEC. 1106.2 FBC P. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |