2021-12-30 09:13:12 | NEW COMMERCIAL BUILDING |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - |
| |
| 1) PLEASE SHOW THE HOURLY FIRE RATING FOR THE EXTERIOR |
| WALLS THAT ARE 5 FEET FROM THE PROPERTY LINES - FBC |
| TABLE 602 |
| |
| 2) PLEASE SHOW THE RESTROOM AND MOP SINK AREA WALL |
| FINISHES TO COMPLY WITH FBC 1210.2.2 WALLS AND |
| PARTITIONS. |
| WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE |
| SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH, |
| HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS |
| THAN 4 FEET (1219 MM) ABOVE THE FLOOR, (DRYWALL IS NOT |
| CONSIDERED A HARD SURFACE) |
| |
| 3) FINISH SCHEDULE SHOWS WOOD BASE BOARD IN THE |
| RESTROOM - SHOULD BE A NONABSORBENT MATERIAL - FBC |
| 1210.2.1 FLOORS AND WALL BASES. |
| IN OTHER THAN DWELLING UNITS, TOILET, BATHING AND |
| SHOWER ROOM FLOOR FINISH MATERIALS SHALL HAVE A SMOOTH, |
| HARD, NONABSORBENT SURFACE. THE INTERSECTIONS OF SUCH |
| FLOORS WITH WALLS SHALL HAVE A SMOOTH, HARD, |
| NONABSORBENT VERTICAL BASE THAT EXTENDS UPWARD ONTO THE |
| WALLS NOT LESS THAN 4 INCHES (102 MM). |
| |
| 4) PLEASE SHOW THE STAIR HANDRAIL EXTENSIONS - |
| HORIZONTAL AT TOP AND SLOPE AT BOTTOM PER FBC 1014.6 |
| HANDRAIL EXTENSIONS. |
| HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING |
| SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN |
| ADJACENT FLIGHT OF STAIRS OR RAMP RUN. WHERE HANDRAILS |
| ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL |
| EXTEND HORIZONTALLY NOT LESS THAN 12 INCHES (305 MM) |
| BEYOND THE TOP RISER AND CONTINUE TO SLOPE FOR THE |
| DEPTH OF ONE TREAD BEYOND THE BOTTOM RISER. |
| |
| 5) PLEASE SHOW THE TYPE OF TERMITE PROTECTION PER FBC |
| 1816 |
| |
| 6) ACCESSIBLE RESTROOM - PLEASE SHOW THE MIRROR |
| DIMENSIONS FROM THE FINISHED FLOOR TO THE "REFLECTIVE |
| SURFACE" PER FBC A 603.3 MIRRORS. |
| MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| FLOOR OR GROUND. |
| |
| 7) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| PRODUCT APPROVALS FOR THE EXTERIOR DOORS, EXTERIOR |
| WINDOWS AND ROOFING SYSTEMS - ALL PRODUCT APPROVALS |
| NEED TO BE REVIEWED AND MARKED APPROVED BY THE BUILDING |
| DESIGNER OF RECORD IF NOT LISTED BY THE PRODUCT |
| APPROVAL NUMBER ON THE DRAWINGS. FBC WPB 107.3.4 |
| |
| 8) SEPARATE PERMITS ARE REQUIRED FOR - DUMPSTER |
| ENCLOSURE, PARKING LOT, SITE LIGHTING, EXISTING |
| BUILDING DEMO - PLEASE ACKNOWLEDGE THIS. |
| |
| 9) ITEMS SUCH AS ROOFING SYSTEMS, WINDOW AND DOOR |
| PRODUCT APPROVALS, CANOPY DETAILS ETC. MAY BE DEFERRED |
| SUBMITTALS BY LISTING ITEMS TO BE DEFERRED ON THE |
| CONSTRUCTION DOCUMENTS - FBC WPB 107.3.4.1 DEFERRED |
| SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, DEFERRED |
| SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF THE DESIGN |
| THAT ARE NOT SUBMITTED AT THE TIME OF THE APPLICATION |
| AND THAT ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL |
| WITHIN A SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL |
| ITEMS SHALL HAVE THE PRIOR APPROVAL OF THE BUILDING |
| OFFICIAL. THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE SHALL LIST THE DEFERRED SUBMITTALS |
| ON THE CONSTRUCTION DOCUMENTS FOR REVIEW BY THE |
| BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED SUBMITTAL |
| ITEMS SHALL BE SUBMITTED TO THE REGISTERED DESIGN |
| PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL REVIEW |
| THEM AND FORWARD THEM TO THE BUILDING OFFICIAL WITH A |
| NOTATION INDICATING THAT THE DEFERRED SUBMITTAL |
| DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL |
| CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED |
| SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE |
| DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE |
| BUILDING OFFICIAL. |
| |