Plan Review Notes
Plan Review Notes For Permit 21120045
Permit Number 21120045
Review Stop P
Sequence Number 1
Notes
Date Text
2021-12-06 11:08:0512/06/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THIS REVISION APPEARS TO BE DIFFERENT FROM THE
 ORIGINAL PERMIT SUBMITTED FOR MASTER 19060556. A
 SEPARATE PERMIT AND REVIEW ARE REQUIRED FOR ALL TRADES
 AND ZONING PER THE WPB AMENDMENTS TO THE FBC SEC. 105.1
  
 2. THIS APPEARS TO BE A DIFFERENT STRUCTURE AND IF THE
 STRUCTURE IS THE FRONT STRUCTURE IT WILL REQUIRE A SET
 OF PLAN, REVIEW AND A DIFFERENT PERMIT. IF SO MAY USE
 THIS REVISION FOR THE PERMIT AS A MASTER IN THE FRONT
 STRUCTURE SO PLEASE REQUEST A CHANGE TO THE PERMIT
 LIBRARIAN @ [email protected].
  
 3. THE PLUMBING NOTES REFER TO THE 2014 FBC. PLEASE
 CORRECT TO CURRENT EDITION PER THE WPB AMENDMENTS TO
 FBC 102.3 APPLICATION OF REFERENCES.
  
 4. THESE ARE MULTI-FAMILY DWELLINGS, AND WATER USERS
 WILL BE REQUIRED TO INSTALL A BACKFLOW PREVENTION
 ASSEMBLY AT THE POINT OF DELIVERY. THE TYPE OF BACKFLOW
 ASSEMBLY REQUIRED WILL BE DEPENDENT UPON THE DEGREE OF
 HAZARD POSED BY THE WATER USER. A REDUCED PRESSURE ZONE
 BACKFLOW DEVICE WILL BE REQUIRED AT THE WATER METER PER
 THE CITY OF WEST PALM CROSS UTILITIES DEPARTMENT AND
 THEIR CONNECTION CONTROL PROGRAM. A SEPARATE PERMIT IS
 REQUIRED FOR THE BACKFLOW DEVICES PER THE WPB
 AMENDMENTS TO FBC SEC. 105.1.
  
 5. A SUB GAS PERMIT IS REQUIRED BY A LICENSED
 CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS
 TO THE FBC SEC. 105.1. EACH STRUCTURE REQUIRES A GAS
 PERMIT.
  
 A. HOT WATER LINES UNDER SLAB NOT IN CONDITION SPACE
 NEED TO BE INSULATED WITH A MINIMUM R-3 PER THE 2020
 FBC SEC. RE 403.5.3. PLEASE PLACE A NOTE.
  
 B. IF THE TANK-LESS HAS A CONDENSATE IT NEEDS TO BE 1'
 AWAY FROM THE STRUCTURE PER THE 2020 FBC SEC. R318.5.
  
 C. NOTE: YOU MAY CHOOSE TO HAVE A GAS REVIEW DONE THIS
 TIME AND ADDRESS THE COMMENTS ABOVE. THIS WILL HAVE THE
 GAS APPROVE FOR A SUB PERMIT, OR IF YOU DECIDED NOT TO
 ADDRESS THESE COMMENTS, PLEASE PUT A NOTE ON THE GAS
 HEATER (A SEPARATE PERMIT BY A LICENSED CONTRACTOR FOR
 THE GAS SYSTEM). THEN PLEASE TAKE OFF ANY GAS SHOWN ON
 PLANS; THESE COMMENTS CAN BE FORWARD TO THE GAS
 CONTRACTOR FOR REFERENCE. AN N WILL BE PUT ON THIS
 REVIEW, WHICH STANDS FOR NOT REQUIRED, BUT A SUB PERMIT
 WON'T BE ISSUED ONCE A REVIEW IS DONE FOR THAT SUB
 PERMIT, SO PLEASE BE ADVISED ON THIS PROCEDURE.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved