Date |
Text |
2021-12-06 11:08:05 | 12/06/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. THIS REVISION APPEARS TO BE DIFFERENT FROM THE |
| ORIGINAL PERMIT SUBMITTED FOR MASTER 19060556. A |
| SEPARATE PERMIT AND REVIEW ARE REQUIRED FOR ALL TRADES |
| AND ZONING PER THE WPB AMENDMENTS TO THE FBC SEC. 105.1 |
| |
| 2. THIS APPEARS TO BE A DIFFERENT STRUCTURE AND IF THE |
| STRUCTURE IS THE FRONT STRUCTURE IT WILL REQUIRE A SET |
| OF PLAN, REVIEW AND A DIFFERENT PERMIT. IF SO MAY USE |
| THIS REVISION FOR THE PERMIT AS A MASTER IN THE FRONT |
| STRUCTURE SO PLEASE REQUEST A CHANGE TO THE PERMIT |
| LIBRARIAN @ [email protected]. |
| |
| 3. THE PLUMBING NOTES REFER TO THE 2014 FBC. PLEASE |
| CORRECT TO CURRENT EDITION PER THE WPB AMENDMENTS TO |
| FBC 102.3 APPLICATION OF REFERENCES. |
| |
| 4. THESE ARE MULTI-FAMILY DWELLINGS, AND WATER USERS |
| WILL BE REQUIRED TO INSTALL A BACKFLOW PREVENTION |
| ASSEMBLY AT THE POINT OF DELIVERY. THE TYPE OF BACKFLOW |
| ASSEMBLY REQUIRED WILL BE DEPENDENT UPON THE DEGREE OF |
| HAZARD POSED BY THE WATER USER. A REDUCED PRESSURE ZONE |
| BACKFLOW DEVICE WILL BE REQUIRED AT THE WATER METER PER |
| THE CITY OF WEST PALM CROSS UTILITIES DEPARTMENT AND |
| THEIR CONNECTION CONTROL PROGRAM. A SEPARATE PERMIT IS |
| REQUIRED FOR THE BACKFLOW DEVICES PER THE WPB |
| AMENDMENTS TO FBC SEC. 105.1. |
| |
| 5. A SUB GAS PERMIT IS REQUIRED BY A LICENSED |
| CONTRACTOR FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS |
| TO THE FBC SEC. 105.1. EACH STRUCTURE REQUIRES A GAS |
| PERMIT. |
| |
| A. HOT WATER LINES UNDER SLAB NOT IN CONDITION SPACE |
| NEED TO BE INSULATED WITH A MINIMUM R-3 PER THE 2020 |
| FBC SEC. RE 403.5.3. PLEASE PLACE A NOTE. |
| |
| B. IF THE TANK-LESS HAS A CONDENSATE IT NEEDS TO BE 1' |
| AWAY FROM THE STRUCTURE PER THE 2020 FBC SEC. R318.5. |
| |
| C. NOTE: YOU MAY CHOOSE TO HAVE A GAS REVIEW DONE THIS |
| TIME AND ADDRESS THE COMMENTS ABOVE. THIS WILL HAVE THE |
| GAS APPROVE FOR A SUB PERMIT, OR IF YOU DECIDED NOT TO |
| ADDRESS THESE COMMENTS, PLEASE PUT A NOTE ON THE GAS |
| HEATER (A SEPARATE PERMIT BY A LICENSED CONTRACTOR FOR |
| THE GAS SYSTEM). THEN PLEASE TAKE OFF ANY GAS SHOWN ON |
| PLANS; THESE COMMENTS CAN BE FORWARD TO THE GAS |
| CONTRACTOR FOR REFERENCE. AN N WILL BE PUT ON THIS |
| REVIEW, WHICH STANDS FOR NOT REQUIRED, BUT A SUB PERMIT |
| WON'T BE ISSUED ONCE A REVIEW IS DONE FOR THAT SUB |
| PERMIT, SO PLEASE BE ADVISED ON THIS PROCEDURE. |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| |
| LUIS A. CRESPO |
| PLUMBING PLAN EXAMINER / INSPECTOR |
| EMAIL: [email protected] OFFICE: 561 805-6720 |
| |