Plan Review Notes For Permit 21120011 |
Permit Number |
21120011 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-12-07 11:57:53 | 1ST REVIEW FBC-2020 MECHANICAL | | PERMIT-21120011 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE | | FBC M- FLORIDA MECHANICAL CODE | | FBC EC- FLORIDA ENERGY CONSERVATION | | FBC FG- FLORIDA FUEL GAS | | FBC EX- FLORIDA EXISTING BUILDING CODE | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING | | CALCULATIONS FOR THE NEW CONDITIONED SPACES FOR THE 1ST | | AND 2ND FLOORS. | | | | 2) PLEASE SHOW THE MAKEUP AIR FOR THE 800 CFM RANGE | | HOOD IN THE KITCHEN. FBC RES M1503.4 EXCEPTION B BELOW: | | | | (B) MORE THAN 400 CUBIC FEET PER MINUTE BUT NO MORE | | THAN 800 CUBIC FEET PER MINUTE IF THERE ARE NO GRAVITY | | VENT APPLIANCES WITHIN THE CONDITIONED LIVING SPACE OF | | THE STRUCTURE. | | | | 3) PLEASE SHOW THE CONDENSATION PIPE, MATERIAL AND | | TERMINATION LOCATION. FBC RES M1411 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|