Plan Review Notes
Plan Review Notes For Permit 21111211
Permit Number 21111211
Review Stop P
Sequence Number 1
Notes
Date Text
2021-12-15 14:57:001ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21111211
 12/15/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P2.1 & P5.1: THE ISO SHOWS THE SINK PUMP VENT
 PIPE CONNECTING TO THE EXISTING RISER BUT SINK PUMP
 DETAIL SHOWS AN AAV- WHICH IS CORRECT?- SEC 906.5 FBC
 P.
  
 2) P2.1: PLEASE SHOW THE LOCATIONS OF THE REQUIRED
 CHECK VALVE AND FULL OPEN VALVES ON THE DISCHARGE PIPE,
 AND SHOW HOW ACCESS TO THE VALVES WILL BE PROVIDED-
 SEC. 712.2 FBC P.
  
 3) A1.1: SHOW THE CLEAR FLOOR SPACE APPROACH DIAGRAMS
 AND DIMENSIONS AT WATER DISPENSER, DISHWASHER AND
 REFRIGERATOR- SECTIONS 305, 804.6.3 & 804.6.6 FBC ACC.
  
 4) A1.1 & A3.2: PROVIDE AN ELEVATION DETAIL OR NOTE TO
 VERIFY THE FREEZER INSIDE THE REFRIGERATOR HAS A
 MINIMUM OF 50 PERCENT OF FREEZER SPACE 54-INCHES
 MAXIMUM FROM THE FINISHED FLOOR.
  
 D) A1.1 & A3.2: SHOW THE HEIGHT OF THE WATER DISPENSER
 CONTROL AND INDICATE COMPLIANCE WITH SEC. 308- REACH
 RANGES, AND 309- OPERABLE PARTS. PLEASE SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR THE DISPENSER
 INDICATING ADA COMPLIANCE- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  