2021-12-15 14:57:00 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 21111211 |
| 12/15/21 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET P2.1 & P5.1: THE ISO SHOWS THE SINK PUMP VENT |
| PIPE CONNECTING TO THE EXISTING RISER BUT SINK PUMP |
| DETAIL SHOWS AN AAV- WHICH IS CORRECT?- SEC 906.5 FBC |
| P. |
| |
| 2) P2.1: PLEASE SHOW THE LOCATIONS OF THE REQUIRED |
| CHECK VALVE AND FULL OPEN VALVES ON THE DISCHARGE PIPE, |
| AND SHOW HOW ACCESS TO THE VALVES WILL BE PROVIDED- |
| SEC. 712.2 FBC P. |
| |
| 3) A1.1: SHOW THE CLEAR FLOOR SPACE APPROACH DIAGRAMS |
| AND DIMENSIONS AT WATER DISPENSER, DISHWASHER AND |
| REFRIGERATOR- SECTIONS 305, 804.6.3 & 804.6.6 FBC ACC. |
| |
| 4) A1.1 & A3.2: PROVIDE AN ELEVATION DETAIL OR NOTE TO |
| VERIFY THE FREEZER INSIDE THE REFRIGERATOR HAS A |
| MINIMUM OF 50 PERCENT OF FREEZER SPACE 54-INCHES |
| MAXIMUM FROM THE FINISHED FLOOR. |
| |
| D) A1.1 & A3.2: SHOW THE HEIGHT OF THE WATER DISPENSER |
| CONTROL AND INDICATE COMPLIANCE WITH SEC. 308- REACH |
| RANGES, AND 309- OPERABLE PARTS. PLEASE SUBMIT |
| MANUFACTURER'S SPECIFICATIONS FOR THE DISPENSER |
| INDICATING ADA COMPLIANCE- SEC. 107.2.1 WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |