Plan Review Notes For Permit 21111179 |
Permit Number |
21111179 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-12-20 11:19:11 | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | BUILDING REVIEW DENIED: | | | | FBC B 107.2.1, PLEASE HAVE THE DESIGN PROFESSIONAL | | INDICATE WHICH OPTION IS TO BE USED FOR DESIGN | | PRESSURES BY CIRCLING THE SELECTED OPTION ON WINDLOAD | | SHEET. | | FBC B 107.2.1, PLEASE INDICATE THE OPTIONS TO BE USED | | WITHIN THE SUBMITTED PRODUCT APPROVAL FOR THE SINGLE | | HUNG WINDOW. | | FBC B 107.2.1, PLEASE SUBMIT/ PROVIDE WINDOW COVERING | | (IMPACT RESISTANT SHUTTER) INFORMATION AS THE | | INFORMATION SUBMITTED INDICATES THAT THIS IS A | | NON-IMPACT WINDOW. | | |
|