 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1, PLEASE HAVE THE DESIGN PROFESSIONAL
 INDICATE WHICH OPTION IS TO BE USED FOR DESIGN
 PRESSURES BY CIRCLING THE SELECTED OPTION ON WINDLOAD
 SHEET.
 FBC B 107.2.1, PLEASE INDICATE THE OPTIONS TO BE USED
 WITHIN THE SUBMITTED PRODUCT APPROVAL FOR THE SINGLE
 HUNG WINDOW.
 FBC B 107.2.1, PLEASE SUBMIT/ PROVIDE WINDOW COVERING
 (IMPACT RESISTANT SHUTTER) INFORMATION AS THE
 INFORMATION SUBMITTED INDICATES THAT THIS IS A
 NON-IMPACT WINDOW.
  