Plan Review Notes For Permit 21111137 |
Permit Number |
21111137 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-01-27 08:48:59 | 1ST REVIEW FBC-2020 MECHANICAL | | PERMIT-21111137 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE | | FBC M- FLORIDA MECHANICAL CODE | | FBC EC- FLORIDA ENERGY CONSERVATION | | FBC FG- FLORIDA FUEL GAS | | FBC EX- FLORIDA EXISTING BUILDING CODE | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE COMMON HALL IS A 1-HOUR RATED EXIT ENCLOSURE, | | PLEASE SHOW THAT THE MECHANICAL SYSTEM FOR THIS COMMON | | HALL WILL MEET THE REQUIREMENTS OF FBC M 601.3-3 | | | | 2) THE EF-1 EXHAUST DUCT IS PENETRATING A RATED WALL AT | | THE WOMEN?S ADA TOILET. PLEASE SHOW HOW THE PENETRATION | | IN THE RATED WALL SHALL BE PROTECTED. FBC M 607 | | | | 3) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON | | EACH USE OF SPACE. FBC M 403.3.1.1 AND TABLE 403.3.1.1 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|