Plan Review Notes
Plan Review Notes For Permit 21111137
Permit Number 21111137
Review Stop E
Sequence Number 1
Notes
Date Text
2022-02-02 09:17:34ELECTRIC REVIEW FAILED
 1) PLEASE DETAIL SIZE OF SERVICE ENTRANCE CONDUCTORS IN
 GUTTER FEEDING PANELS? A,B,C?. NEC 215.5 DIAGRAMS OF
 FEEDERS
 2) NO ELECTRICAL LOADS ARE DETAILED FOR PANELS ?B AND
 C?. PLEASE DETAIL OCCUPANCY TYPE AND EXPECTED LOADS FOR
 THESE PANELS. NEC 215.5 DIAGRAMS OF FEEDERS
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  