2022-02-09 09:56:36WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21111137
 ADD: 1551 FORUM PLACE PL. # 100A
 CONT: HALLMARK CONSTRUCTION LLC
 TEL: 561-586-7664
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. FEB. 09/2022
 ACTION: DENIED
  
 1) SHEET A1 FLOOR PLAN VS ROOM FINISH SCHEDULE. FINISH
 SCHEDULE, ROOMS 117 STAFF RESTROOM, 121 MENS RESTROOM &
 122 WOMENS RESTROOM ALL SHOW ALL WALLS TO HAVE A PAINT
 FINISH.
 2020 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS COMMENT
 IS A RESULT OF THE BUILDING OFFICIAL INTERPRETATION ON
 06/2020. IN BATHROOMS, RESTROOMS & SERVICE SINK AREAS
 EPOXY PAINT IS NO LONGER CONSIDERED A SMOOTH HARD,
 NON-ABSORBENT SURFACE.
  
 1A) 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF
 SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT
 LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A
 TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
 1B) 2509.1. WET AREAS. SHOWERS AND PUBLIC TOILET WALLS
 SHALL COMPLY WITH 1210.2.
  
 1C) 1210.2. FINISH MATERIALS. WALLS, BASE, FLOORS AND
 PARTITIONS IN TOILET AND BATHROOMS SHALL COMPLY WITH
 SECTIONS 1210.1 THROUGH 1210.4.
  
 2) SHEET A-2 THE REFLECTIVE CEILING PLAN SHOWS EXIT
 SIGNS AND DIRECTIONAL EXIT SIGNS, WHAT APPEARS MISSING
 IN THE END OF HALL 116 A DIRECTIONAL EXIT LIGHT TOWARDS
 THE COMMON HALL AND A DIRECTIONAL EXIT LIGHT IN THE
 COMMON CORRIDOR AND EXIT LIGHT AT THE EXIT. 2020
 FBC-BUILDING CODE 1013.1.
  
 3) SHEET A3 RESTROOM ELEVATIONS THE REAR ELEVATION OF
 THE WATER CLOSET MISSING THE ONE-FOOT MEASUREMENT FROM
 THE CENTERLINE OF THE WATER CLOSET. 2020
 FBC-ACCESSIBILITY CODE SECTION 604.5.1 THE SIDE WALL
 GRAB BAR SHALL BE 42 INCHES (1065 MM) LONG MINIMUM,
 LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE REAR WALL
 AND EXTENDING 54 INCHES (1370 MM) MINIMUM FROM THE REAR
 WALL.
  
 4A) SHEET A4 ELEVATIONS. DETAIL 2, 3, 5, 6 & 7 ALL SHOW
 THE BASE CABINETS AND TOP OF COUNTER TOP AT 36 INCHES.
 2020 FBC-ACCESSIBILITY CODE 902.1. WORK SURFACES SHALL
 COMPLY WITH 902.3. ADVISORY 902.1 GENERAL. SAMPLES OF
 WORK SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS,
 STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER
 TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON
 COUNTERS, AND WHERE COVERED BY THE ADA SCOPING
 PROVISIONS, EMPLOYEE WORKSTATIONS. 902.3 HEIGHT. THE
 TOPS OF WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 4B) SHEET A4 ELEVATIONS. DETAILS 5,6 & 7 ALL SHOW SINKS
 /COUNTER TOPS AT A ELEVATION OF 36 INCHES ABOVE THE
 FINISH FLOOR. 2020 FBC-ACCESSIBILITY CODE SECTION 606.3
 HEIGHT. LAVATORIES AND SINKS SHALL BE INSTALLED WITH
 THE FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE
 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 5) SHEET A1 SHOWS AT THE REAR OF THE TENANT SPACE THERE
 IS A ONE-HOUR FIRE RATED SHARED CORRIDOR. SHEET M-1
 SHOWS AIR CONDITIONING DUCTS AND RETURN DUCTS ENTERING
 THE ONE-HOUR FIRE RATED CORRIDOR WITH NO FIRE DAMPER.
 PLEASE SHOW COMPLIANCE WITH THE 2020 FBC-BUILDING CODE
 SECTION 717.5.2.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  