Plan Review Notes
Plan Review Notes For Permit 21111110
Permit Number 21111110
Review Stop E
Sequence Number 1
Notes
Date Text
2022-03-08 09:00:40ELECTRIC REVIEW FAILED
 1)PLEASE HAVE ROOMS LABELED, MEETING, COMPLY WITH NEC
 210.71 (A)(B) (1) (2), MEETING ROOMS AND CONFERENCE
 ROOM RECEPTACLES,
 2)PLEASE HAVE EXAM ROOM #139 COMPLY WITH NEC 517.13
 GROUNDING OF RECEPTACLES
 3) LOW VOLTAGE REQUIRES SEPERATE PERMIT. PLEASE PROVIDE
 A NOTE STATING THIS REQUIREMENT
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  