2021-12-08 09:13:391) WITHOUT KNOWING THE FLOW OF THIS BUSINESS I AM
 CONSIDERING THE MEETING AREA AS A CONFERENCE ROOM AREA.
 THIS WOULD BE CALCULATED DIFFERENTLY FROM THE BREAK
 AREA. THE SUBMITTED OUTDOOR AIR CALCULATIONS USE THE
 SAME OCCUPANT DENSITY, PEOPLE OUTDOOR AIRFLOW RATE IN
 BREATHING ZONE AND AREA OUTDOOR AIRFLOW RATE IN
 BREATHING ZONE FOR ALL THREE AREAS WHICH IS THE OFFICE
 SPACES OCCUPANCY DENSITY. IF THE ENTIRE AREA IS TO BE
 CONSIDERED OFFICE SPACE THEN PLEASE RELABEL THE DRAWING
 TO REFLECT THIS. FBC M 403.3.1.1 AND TABLE 403.3.1.1
  
 2) PLEASE SHOW HOW THE OUTDOOR AIR WILL BE INTRODUCED
 TO THIS ENTIRE TENANT SPACE SINCE YOU ARE USING
 MINI-SPLITS. FBC 107.2.1
  