Plan Review Notes For Permit 21111056 |
Permit Number |
21111056 |
|
Review Stop |
B |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2022-01-18 11:25:12 | JONATHAN BROOKS JR. | | BUILDING PLANS EXAMINER | | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM | | PHONE (561) 805-6656 | | EMAIL: [email protected] | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | CITY HALL, OR EMAIL [email protected] AND REQUEST | | THAT IT BE CONVERTED TO PROJECTDOX. | | | | 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT | | APPROVAL FL16709-R9 SELECTED SYSTEM NO W-4; EXPOSURE | | (B); ENCLOSURE (ENCLOSED); ROOF HEIGHT (15 < H < 20); | | ULTIMATE WIND SPEED (160), IS NOT CORRECT. THE CORRECT | | EXPOSURE IS EXPOSURE C, THE ULTIMATE WIND SPEED FOR THE | | LISTED ADDRESS IS 170 (MPH). PLEASE SELECT THE CORRECT | | OPTIONS; CONSIDER USING FL16709-R9 SYSTEM NO. W-4; | | EXPOSURE C; ENCLOSED; ZONES 1 PRIME, 1, 2, & 3; 15 < H | | < 20; 170 (MPH). | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. | | |
|