Plan Review Notes
Plan Review Notes For Permit 21111056
Permit Number 21111056
Review Stop B
Sequence Number 3
Notes
Date Text
2021-12-29 13:26:00JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. FBC B 107.2.1. SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL16709-R8 HAS BEEN REVISED TO FL16709-R9.
 PLEASE PROVIDE A COMPLETE SET OF PRODUCT APPROVALS.
 INCLUDE COVER PAGE, EVALUATION REPORTS AND INSTALLATION
 INSTRUCTIONS FOR SYSTEM USED. ALL APPLICABLE DETAILS
 AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE
 PRODUCT APPROVAL DRAWINGS.
 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL16709-R9 COVERS MULTIPLE ROOF SYSTEM TYPES
 A-2 THROUGH E, NO. W-1 THRU W-5. PLEASE SELECT SYSTEM
 NO.; EXPOSURE; ENCLOSURE; ROOF HEIGHT; ZONE AND
 ULTIMATE WIND SPEED. ALL APPLICABLE DETAILS AND
 ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT
 APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT
 SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING.
 3. FBC B 107.2.1. SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL5374-R4 IS THE 2014 CODE VERSION AND IS NO
 LONGER VALID. PLEASE PROVIDE A COMPLETE SET OF 2020
 CODE VERSION PRODUCT APPROVALS/NOA?S FOR THE PROPOSED
 HIP & RIDGE METAL TO BE USED. INCLUDE COVER PAGE,
 EVALUATION REPORTS AND INSTALLATION INSTRUCTIONS FOR
 SYSTEM USED. ALL APPLICABLE DETAILS AND ATTACHMENTS
 MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL
 DRAWINGS. (FL5374-R6)
 4. FBC R 301 FAC9N-3 SUBMITTED MIAMI-DADE COUNTY NOA
 21-0315.02 COVERS MULTIPLE ATTACHMENT SYSTEMS;
 MECHANICAL, ADHESIVE AND MORTAR SET. SELECT SYSTEM TO
 BE USED. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE
 CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
 DETAILS AND ATTACHMENTS NOT SPECIFICALLY COVERED IN
 PRODUCT APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING.
 5. FBC B 107.2.1 FBC EB 706.1 SUBMITTED ROOF
 DRAWING/SKETCH LISTS FLAT/LOW ROOF SLOPE AS 0:12; LOW
 SLOPE ROOFS MUST SHOW POSITIVE DRAINAGE. PROVIDE METHOD
 OF PROVIDING POSITIVE DRAINAGE.
 6. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF
 DIAGRAM/SKETCH AND CORRECT FLAT ROOF MEAN ROOF
 HEIGHT(S). PAPA INDICATES UPPER LEVEL.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  