Plan Review Notes
Plan Review Notes For Permit 21110989
Permit Number 21110989
Review Stop E
Sequence Number 2
Notes
Date Text
2022-02-24 15:02:04CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) THE FOLLOWING EQUIPMENT NEEDS TO SHOW THE LISTING
 FOR THE EQUIPMENT
  
 INSTALLATION AND USE. LISTED OR LABELED EQUIPMENT SHALL
 BE INSTALLED AND USED IN ACCORDANCE WITH ANY
 INSTRUCTIONS INCLUDED
 IN THE LISTING OR LABELING.
 LISTING. PRODUCT TESTING, EVALUATION, AND LISTING
 (PRODUCT CERTIFICATION) SHALL BE PERFORMED BY
 RECOGNIZED QUALIFIED ELECTRICAL
 TESTING LABORATORIES AND SHALL BE IN ACCORDANCE WITH
 APPLICABLE PRODUCT STANDARDS RECOGNIZED AS ACHIEVING
 EQUIVALENT
 AND EFFECTIVE SAFETY FOR EQUIPMENT INSTALLED TO COMPLY
 WITH THIS CODE.
  
 SOLAR TREE, BATTERY RACK, BESS NEA CONTROLLER, BESS
 IMM, BESS CONTROL CABINET, BESS FIREWALL, 7580 PT
 OVERALL DIMS, OPTOS, OUTDOOR LIQUID COOLING RACK,
 AIR INFLATOR, INVERTER MPS125 EHV, NBDC, NBSK.
  
 2) PAGE E-201
  
 FAULT CURRENT CALCULATION 110.9, 110.10
 OVERCURRENT PROTECTION FOR NBDC UNITS 500, 200 NEEDS TO
 SHOW SOMWHERE WHAT SIZE BREAKERS ARE BEING USED.
 LISTING FOR THE LINE SIDE TAP IN THE NBSK 112500S
 110.3, 110.9, 110.10