2022-02-24 15:02:04 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| PART VIII ELECTRICAL |
| NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| |
| FLORIDA BUILDING CODE 2020 7TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED |
| NFPA 70 2017 EDITION |
| |
| JAKE LEAHY |
| ELECTRICAL PLANS EXAMINER II |
| 561-805-6713 |
| [email protected] |
| |
| 1) THE FOLLOWING EQUIPMENT NEEDS TO SHOW THE LISTING |
| FOR THE EQUIPMENT |
| |
| INSTALLATION AND USE. LISTED OR LABELED EQUIPMENT SHALL |
| BE INSTALLED AND USED IN ACCORDANCE WITH ANY |
| INSTRUCTIONS INCLUDED |
| IN THE LISTING OR LABELING. |
| LISTING. PRODUCT TESTING, EVALUATION, AND LISTING |
| (PRODUCT CERTIFICATION) SHALL BE PERFORMED BY |
| RECOGNIZED QUALIFIED ELECTRICAL |
| TESTING LABORATORIES AND SHALL BE IN ACCORDANCE WITH |
| APPLICABLE PRODUCT STANDARDS RECOGNIZED AS ACHIEVING |
| EQUIVALENT |
| AND EFFECTIVE SAFETY FOR EQUIPMENT INSTALLED TO COMPLY |
| WITH THIS CODE. |
| |
| SOLAR TREE, BATTERY RACK, BESS NEA CONTROLLER, BESS |
| IMM, BESS CONTROL CABINET, BESS FIREWALL, 7580 PT |
| OVERALL DIMS, OPTOS, OUTDOOR LIQUID COOLING RACK, |
| AIR INFLATOR, INVERTER MPS125 EHV, NBDC, NBSK. |
| |
| 2) PAGE E-201 |
| |
| FAULT CURRENT CALCULATION 110.9, 110.10 |
| OVERCURRENT PROTECTION FOR NBDC UNITS 500, 200 NEEDS TO |
| SHOW SOMWHERE WHAT SIZE BREAKERS ARE BEING USED. |
| LISTING FOR THE LINE SIDE TAP IN THE NBSK 112500S |
| 110.3, 110.9, 110.10 |