Plan Review Notes
Plan Review Notes For Permit 21110989
Permit Number 21110989
Review Stop B
Sequence Number 2
Notes
Date Text
2022-02-15 14:15:54CAR CHARGING STATIONS
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) SPOT LIGHT SOLAR STRUCTURE IS SUBJECT TO WIND LOADS
 - PLEASE PROVIDE DETAILS FROM A DESIGN PROFESSIONAL TO
 MEET THE REQUIRED WIND LOADS FBC 1609
  
 2) PLEASE PROVIDE THE SOLAR CANOPY DETAILS FROM A
 DESIGN PROFESSIONAL - FOR THE SOLAR CANOPY SHOWN OVER
 THE TABLE (SOLAR ZONE) - WILL NEED TO MEET THE REQUIRED
 WIND LOADS FBC 1609
  
 3) SOLAR CANOPY DETAILS PROVIDED - DRAWING T1.0 AND THE
 PROVIDED CALCULATIONS SHOWS WIND DESIGN AS RISK
 CATEGORY II WITH WIND SPEED OF 169 MPH = RISK CATEGORY
 II REQUIRES A DESIGN WIND SPEED OF 170 MPH PER FBC WPB
 SECTION 120
  
 4) A SEPARATE PERMIT IS REQUIRED FOR THE MONUMENT
 SIGNAGE.
  
  
  