Plan Review Notes For Permit 21110989 |
Permit Number |
21110989 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-01-11 09:10:51 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | 1) PLEASE PROVIDE A COST BREAK DOWN OF ALL MATERIALS | | (CUSTOMER AND CONTRACTOR SUPPLIED) AND LABOR FOR THIS | | PROJECT. | | | | 2) PROVIDE LISTINGS AND CUT SHEETS FOR "ALL" EQUIPMENT | | BEING USED ON THIS PROJECT. 110.3 | | | | 3) DISPENSERS SHOW NO OVER CURRENT PROTECTION OTHER | | THAN THE MAIN AT 2500 AMPERES. | | | | 4) SEPARATE PERMIT FOR SIGNS REQUIRED. | | | | 5) NO DETAILS FOR CANOPY AND TREE SOLAR PROJECTS. |
|