2022-01-11 09:10:51ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) PLEASE PROVIDE A COST BREAK DOWN OF ALL MATERIALS
 (CUSTOMER AND CONTRACTOR SUPPLIED) AND LABOR FOR THIS
 PROJECT.
  
 2) PROVIDE LISTINGS AND CUT SHEETS FOR "ALL" EQUIPMENT
 BEING USED ON THIS PROJECT. 110.3
  
 3) DISPENSERS SHOW NO OVER CURRENT PROTECTION OTHER
 THAN THE MAIN AT 2500 AMPERES.
  
 4) SEPARATE PERMIT FOR SIGNS REQUIRED.
  
 5) NO DETAILS FOR CANOPY AND TREE SOLAR PROJECTS.