2022-06-22 08:13:44ADDITION AND ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) ROOFING PRODUCT APPROVAL (18-0919.07) SHOWS THE
 MAXIMUM WIND DESIGN PRESSURE OF (-52) - SEE GENERAL
 LIMITATION NUMBER 7 ON THE PRODUCT APPROVAL - PLEASE
 PROVIDE SIGNED AND SEALED ADDITIONAL ATTACHMENT DETAILS
 FROM A DESIGN PROFESSIONAL FOR THE ROOFING WIND ZONES
 WHICH REQUIRE A HIGHER WIND DESIGN PRESSURE PER DRAWING
 S1.
  
 2) ROOFING PRODUCT APPROVAL (22-0107.2) PLEASE CIRCLE
 THE ROOF SYSTEM TO BE USED IN THE PRODUCT APPROVAL -
 SEE GENERAL LIMITATION NUMBER 7 ON THE PRODUCT APPROVAL
 - PLEASE PROVIDE SIGNED AND SEALED ADDITIONAL
 ATTACHMENT DETAILS FROM A DESIGN PROFESSIONAL FOR THE
 ROOFING WIND ZONES WHICH REQUIRE A HIGHER WIND DESIGN
 PRESSURE PER DRAWING S1.
  
 3) (THE 18" SHOWN ON THE DRAWING IS FROM THE HINGE SIDE
 - NEEDS TO BE FROM THE LATCH SIDE) ACCESSIBLE RESTROOM
 - PLEASE SHOW THE DOOR MANEUVERING CLEARANCE FROM
 INSIDE THE REST ROOM (18" BESIDE THE LATCH SIDE) TO
 EXIT THE RESTROOM.
  
 4) ROOFING SYSTEMS MAY BE DEFERRED SUBMITTALS BY
 LISTING ITEMS TO BE DEFERRED ON THE CONSTRUCTION
 DOCUMENTS - 107.3.4.1 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
  
  
  
  
  
  
  
  
  