2022-04-28 10:29:45 | ADDITION AND ALTERATION |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - |
| |
| 1) ROOFING PRODUCT APPROVAL (18-0919.07) SHOWS THE |
| MAXIMUM WIND DESIGN PRESSURE OF (-52) - SEE GENERAL |
| LIMITATION NUMBER 7 ON THE PRODUCT APPROVAL - PLEASE |
| PROVIDE SIGNED AND SEALED ADDITIONAL ATTACHMENT DETAILS |
| FROM A DESIGN PROFESSIONAL FOR THE ROOFING WIND ZONES |
| WHICH REQUIRE A HIGHER WIND DESIGN PRESSURE PER DRAWING |
| S1. |
| |
| 2) ROOFING PRODUCT APPROVAL (16-1206.02) IS EXPIRED. |
| |
| 3) ROOFING PRODUCT APPROVAL (16-1206.02) SHOWS A |
| MAXIMUM WIND DESIGN PRESSURE OF (-45) - SEE GENERAL |
| LIMITATION NUMBER 7 ON THE PRODUCT APPROVAL - PLEASE |
| PROVIDE SIGNED AND SEALED ADDITIONAL ATTACHMENT DETAILS |
| FROM A DESIGN PROFESSIONAL FOR THE ROOFING WIND ZONES |
| WHICH REQUIRE A HIGHER WIND DESIGN PRESSURE PER DRAWING |
| S1. |
| |
| 4) ACCESSIBLE RESTROOM - PLEASE SHOW THE LOCATION |
| DIMENSIONS FOR THE TOILET REAR GRAB BAR FROM THE CENTER |
| OF THE TOILET PER FBC A 604.5.2 REAR WALL. |
| THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG |
| MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24 |
| INCHES (610 MM) MINIMUM ON THE OTHER SIDE. |
| |
| 5) ACCESSIBLE RESTROOM - PLEASE USE THE |
| WORDS"REFLECTING SURFACE" WHEN REFERRING TO THE |
| DIMENSION FROM THE FLOOR TO THE BOTTOM OF REFLECTIVE |
| SURFACE OF THE MIRROR PER FBC A 603.3 MIRRORS. |
| MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| FLOOR OR GROUND. |
| |
| 6) ACCESSIBLE RESTROOM - PLEASE SHOW THE DOOR |
| MANEUVERING CLEARANCE (18" BESIDE THE LATCH SIDE) TO |
| EXIT THE RESTROOM. |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |