Plan Review Notes For Permit 21110918 |
Permit Number |
21110918 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-12-29 16:39:27 | 1ST REVIEW FBC-2020 MECHANICAL | | PERMIT-21110918 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE | | FBC M- FLORIDA MECHANICAL CODE | | FBC EC- FLORIDA ENERGY CONSERVATION | | FBC FG- FLORIDA FUEL GAS | | FBC EX- FLORIDA EXISTING BUILDING CODE | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PLEASE PROVIDE THE CONDENSATE PIPE MATERIAL, SIZE | | AND TERMINATION LOCATION ON THE EXTERIOR OF THE | | BUILDING. THE MECHANICAL CONDENSATE CANNOT BE DRAINED | | TO THE SANITARY SYSTEM. FBC M30 | | | | 2) PLEASE SHOW THAT ALL EXHAUST TERMINATION LOCATIONS | | MEET THE REQUIREMENTS OF 3 FEET FROM PROPERTY LINES AND | | 3 FEET FROM OPERABLE OPENINGS. FBC M 501.3 | | | | 3) ARE THE TENANT SPACES SEPARATED WITH A RATED WALL? | | IF SO PLEASE SHOW THE PROTECTION WHERE EF-6 PENETRATES | | THE TENANT SEPARATION WALL. FBC M 607 | | | | 4) PLEASE PROVIDE A DETAIL SHOWING THE CONDENSATE UNITS | | TIE DOWN METHOD. FBC 107.2.1 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|