Plan Review Notes
Plan Review Notes For Permit 21110918
Permit Number 21110918
Review Stop M
Sequence Number 1
Notes
Date Text
2021-12-29 16:39:271ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21110918
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE CONDENSATE PIPE MATERIAL, SIZE
 AND TERMINATION LOCATION ON THE EXTERIOR OF THE
 BUILDING. THE MECHANICAL CONDENSATE CANNOT BE DRAINED
 TO THE SANITARY SYSTEM. FBC M30
  
 2) PLEASE SHOW THAT ALL EXHAUST TERMINATION LOCATIONS
 MEET THE REQUIREMENTS OF 3 FEET FROM PROPERTY LINES AND
 3 FEET FROM OPERABLE OPENINGS. FBC M 501.3
  
 3) ARE THE TENANT SPACES SEPARATED WITH A RATED WALL?
 IF SO PLEASE SHOW THE PROTECTION WHERE EF-6 PENETRATES
 THE TENANT SEPARATION WALL. FBC M 607
  
 4) PLEASE PROVIDE A DETAIL SHOWING THE CONDENSATE UNITS
 TIE DOWN METHOD. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  