2021-12-21 16:24:14 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) ON THE LIFE SAFETY PLAN THERE APPEARS TO BE AN |
| INDICATION OF A BBQ/SMOKER IN AN EXTERIOR AREA. |
| |
| THERE IS NO INDICATION OF HOW THIS BBQ/SMOKER WILL BE |
| FUELED NOR WHERE THE FUEL WILL BE STORED. |
| |
| PLEASE PROVIDE DETAILS. |
| |
| |
| 1A) PLEASE PROVIDE THE BBQ/SMOKER MANUFACTURES |
| SPECIFICATIONS/RECOMMENDATIONS TO ENSURE THAT IT WILL |
| BE USED/STORED/OPERATED PER THE MANUFACTURER. |
| |
| |
| 1B) THERE IS AN INDICATION THAT THERE IS A PROPOSED |
| CANOPY OVER THE BBQ AREA. |
| |
| PLEASE CONFIRM AND PROVIDE THE FIRE RETARDENT |
| CERTIFICATION OF ANY PROPOSED CANOPY COVERING OR A NOTE |
| OF ACKNOWLEDGEMENT OF INTENT TO PROVIDE THE REQUIRED |
| CERTIFICATION. |
| |
| |
| 1C) I AM ALSO CONCERNED THAT ANY HEAT GENERATED BY THE |
| BBQ/SMOKER MAY DEGRADE THE CANOPY COVERING MATERIAL |
| OVER TIME CAUSE FAILURE OR FLAME SPREAD. |
| |
| PLEASE PROVIDE A DETAILED REVIEW OF THE PROPOSED |
| HEAT/SMOKE EXHAUST THAT AVOIDS THIS TYPE OF DEGRADATION |
| OF THE CANOPY COVER MATERIAL. |
| |
| |
| 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |