2021-12-01 16:33:25 | 1ST REVIEW FBC-2020 MECHANICAL |
| PERMIT-21110885 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE |
| FBC M- FLORIDA MECHANICAL CODE |
| FBC EC- FLORIDA ENERGY CONSERVATION |
| FBC FG- FLORIDA FUEL GAS |
| FBC EX- FLORIDA EXISTING BUILDING CODE |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE EQUIPMENT SIZING CALCULATIONS HAVE AN ADDRESS OF |
| 1213 N SAPODILLA AVE BUT THE APPLICATION HAS 1225 N |
| SAPODILLA AVE. PLEASE SUBMIT THE ENERGY CALCULATIONS |
| WITH THE CORRECT ADDRESS. FBC 107.2.1 |
| |
| 2) PLEASE PROVIDE A MECHANICAL DRAWING THAT INCLUDES |
| THE DUCTWORK AND SIZES. IF THERE IS A CHANGE AND AN AS |
| BUILT WILL HAVE TO BE COMPLETED AT A LATER DATE THEN IS |
| WHEN AN AS BUILT MUST BE SUBMITTED AS A REVISION. YOU |
| CANNOT PUT A NOTE ON THE MECHANICAL DRAWING WITH NO |
| DUCTWORK SAYING AN AS BUILT WILL BE PROVIDED AT LATER |
| DATE. FBC 107.2.1 |
| |
| 3) PLEASE SHOW THE CONDENSATION PIPE SIZE, MATERIAL AND |
| TERMINATION LOCATION. FBC RES M1411.3 |
| |
| 4) PLEASE SHOW THE EXHAUST DUCT FOR THE BATH FANS AND |
| THE TERMINATION LOCATIONS. FBC RES M1507.4 |
| |
| 5) PLEASE INDICATE IF A HOOD IS TO BE INSTALLED ABOVE |
| THE RANGE. IF SO IS IT VENTED TO THE EXTERIOR? WHAT IS |
| THE CFM?S OF EXHAUST? IS MAKE UP AIR REQUIRED? FBC RES |
| M1503.3 AND 1503.4 |
| |
| 6) PLEASE SHOW THE RETURN AIR PATH FROM ROOMS WITH |
| DOORS BACK TO THE AHU. FBC RES M1602.3 |
| |
| 7) IS THERE GOING TO BE A LAUNDRY AREA IN THIS HOME? IF |
| SO PLEASE SHOW THE DRYER EXHAUST DUCT AND TERMINATION |
| LOCATION. FBC RES M1502 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |