Plan Review Notes For Permit 21110869 |
Permit Number |
21110869 |
|
Review Stop |
SIGNATURE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-11-23 14:27:14 | DISREGARD NOTES IN THIS REVIEW STOP - FIRE ENTERED IN | | ERROR. LEM | 2021-11-22 13:30:34 | SPECIFY DISTANCES FROM HVAC REGISTERS PER TABLE 8.3.2.5 | | NFPA 13 | | SPECIFY MAXIMUM DISTANCE BETWEEN HANGERS PER TABLE | | 9.2.2.1 NFPA 13 | | SPECIFY HOW HYDROSTATIC TESTING WILL BE CONDUCTED PER | | SECTION 25.2.1 NFPA 13 | | |
|